المعاملات الرئيسية

Measuring range
Wafer (flangeless) mag sensor; 8711-M/L line sizes 1½–8 in (40–200 mm); legacy R/U also 0.15/0.30/½/1 in; upper range limit 39 ft/s (12 m/s)
Accuracy
Platform standard reference accuracy 0.25% of rate; optional high accuracy 0.15% of rate (matched sensor/transmitter D1)
Output
Sensor only — pairs with Rosemount 8732/8712 transmitters (4–20 mA HART, FF, Modbus, EtherNet/IP per transmitter)
Supply
Sensor powered/driven by paired transmitter (see 8700M transmitter power tables)
Process connection
Wafer/flangeless between flanges; alignment spacers included; mating flange ratings ASME 150/300, EN PN10/16/25/40, etc.
Wetted parts
Liners PTFE/PFA/ETFE; electrodes 316L SST, Nickel Alloy 276, Tantalum, Pt/Ir, Titanium
تنزيل ورقة المواصفات PDF
المعاملالقيمة
Measuring rangeWafer (flangeless) mag sensor; 8711-M/L line sizes 1½–8 in (40–200 mm); legacy R/U also 0.15/0.30/½/1 in; upper range limit 39 ft/s (12 m/s)
AccuracyPlatform standard reference accuracy 0.25% of rate; optional high accuracy 0.15% of rate (matched sensor/transmitter D1)
OutputSensor only — pairs with Rosemount 8732/8712 transmitters (4–20 mA HART, FF, Modbus, EtherNet/IP per transmitter)
SupplySensor powered/driven by paired transmitter (see 8700M transmitter power tables)
Process connectionWafer/flangeless between flanges; alignment spacers included; mating flange ratings ASME 150/300, EN PN10/16/25/40, etc.
Wetted partsLiners PTFE/PFA/ETFE; electrodes 316L SST, Nickel Alloy 276, Tantalum, Pt/Ir, Titanium
HousingFully welded sealed coil housing
ProtectionPer transmitter/sensor platform hazardous and enclosure options (see PDS)
Media temperatureETFE −29 to 149 °C; PTFE −29 to 177 °C; PFA −29 to 93 °C (manual 8700 series sensor specs)
Ambient temperatureSensor ambient −34 to 65 °C (−30 to 150 °F) per 8700 series manual
CommunicationVia paired transmitter protocols
ApprovalsATEX; IECEx; FM; CSA; PED; CE
Hazardous areaSelectable hazardous-area options on 8700M platform ordering tables
NotesConductivity ≥5 μS/cm. Specs from Emerson PDS 00813-0100-4444 Rev AO Sep 2026 + 8700 Series Sensors Manual.