Fluke

Fluke 922 Airflow Meter

SKU · 30218 · 922 · Brand: Fluke
Available
Quote on request
No online payment · add lines to RFQ BOM

Handheld micromanometer for HVAC. ±4000 Pa, velocity 1–80 m/s, flow/temp, IP40. RFQ + engineer selection help.

Download datasheet PDF

RFQ cart holds BOM lines only. Submit for engineering quote.

Key parameters

Measuring range
Air pressure ±4000 Pa (±16 inH2O / ±40 mbar / ±0.6 PSI); air velocity 250–16000 fpm (1–80 m/s); air flow 0–99999 cfm/m3/hr/l/s; temperature 0–50 °C
Accuracy
Pressure ±1% + 1 Pa (or unit equiv.); velocity ±2.5% of reading at 2000 fpm (10 m/s); temperature ±1% + 2 °C; flow accuracy function of velocity and duct size
Output
Handheld meter display; 99 reading data storage (no analog output)
Supply
Four AA alkaline batteries; typical life 375 h without backlight / 80 h with
Process connection
Hose ports for pitot/static; compatible with most pitot tubes (PT12 12 in optional)
Protection
IP40
Download datasheet PDF

Fits HVAC balancing and duct work where you need a handheld micromanometer for differential air pressure, pitot velocity, calculated flow, and temperature — battery powered, no analog output.

Key advantages

  • Three air measurements — pressure ±4000 Pa, velocity 250–16000 fpm, flow 0–99999 cfm/m³/h (pitot + duct area).
  • Published pressure accuracy — ±1% + 1 Pa (or unit equivalent).
  • 99-reading storage — capture balancing points without a separate logger.
  • Long battery life — four AA; typical 375 h without backlight / 80 h with.

Typical applications

  • HVAC TAB balancing of ducts and air handlers.
  • Filter and damper differential pressure checks.
  • Field velocity surveys with a pitot tube (PT12 12 in optional).

Selection guide

  • Measuring ranges — Air pressure ±4000 Pa (±16 inH2O / ±40 mbar / ±0.6 PSI); air velocity 250–16000 fpm (1–80 m/s); air flow 0–99999 cfm / m³/hr / l/s; temperature 0–50 °C.
  • Accuracy — Pressure ±1% + 1 Pa (or unit equiv.); velocity ±2.5% of reading at 2000 fpm (10 m/s); temperature ±1% + 2 °C; flow accuracy is a function of velocity and duct size.
  • Max pressure at ports — 10 PSI each port (datasheet note). Do not exceed on the hose side.
  • Output — Handheld meter display; 99 reading data storage. No analog output.
  • Supply — Four AA alkaline batteries; typical life 375 h without backlight / 80 h with.
  • Process connection — Hose ports for pitot/static; compatible with most pitot tubes (PT12 12 in optional).
  • IP — IP40.
  • Ambient — Operating 0…+50 °C; storage −40…+60 °C; RH 0–90% non-condensing.

Common mistakes

  • Expecting a 4–20 mA or other analog output — the 922 is a handheld meter with display and 99-reading storage only.
  • Exceeding 10 PSI at either hose port — that is the published max per port.
  • Quoting flow accuracy as a single % — datasheet states flow accuracy depends on velocity and duct size; state duct dimensions in the RFQ if flow is the acceptance metric.
  • Assuming outdoor/washdown IP — rating is IP40; use a different instrument if the site needs higher ingress protection.
  • Forgetting pitot tube length/kit (PT12 12 in optional) when the duct access needs a longer probe.

When to RFQ / what to tell us

  1. Primary measurement: differential pressure, velocity, calculated flow, and/or temperature.
  2. Expected pressure/velocity range and duct size (if flow is required).
  3. Pitot tube need (most tubes compatible; PT12 12 in optional) and ToolPak hanging kit yes/no.
  4. Quantity, ship-to country, and any calibration certificate preference.

Request a Quote · Get selection help

Specs

SpecValue
SKU30218
BrandFluke
Model922
Product typeairflow_meter
Measuring rangeAir pressure ±4000 Pa (±16 inH2O / ±40 mbar / ±0.6 PSI); air velocity 250–16000 fpm (1–80 m/s); air flow 0–99999 cfm/m3/hr/l/s; temperature 0–50 °C
AccuracyPressure ±1% + 1 Pa (or unit equiv.); velocity ±2.5% of reading at 2000 fpm (10 m/s); temperature ±1% + 2 °C; flow accuracy function of velocity and duct size
Output signalHandheld meter display; 99 reading data storage (no analog output)
Supply voltageFour AA alkaline batteries; typical life 375 h without backlight / 80 h with
Process connectionHose ports for pitot/static; compatible with most pitot tubes (PT12 12 in optional)
IP ratingIP40
Ambient temperatureOperating 0 to +50 °C; storage −40 to +60 °C; RH 0–90% non-condensing
DisplayBright backlit display; Min/Max/Average/Hold
ApprovalsEN61326-1; MIL-PRF-28800F Class 3 (vibration)
MountingHandheld; optional ToolPak magnetic hanging kit
NotesMax pressure at each port 10 PSI. Specs from Fluke 922 datasheet 2791462 D-EN-N Rev C.

Documents

FAQ

Q: Does the Fluke 922 provide a 4–20 mA output? A: No. It is a handheld display meter with 99-reading storage. If you need continuous analog output to a PLC, select a different instrument family.

Q: What limits velocity and flow accuracy? A: Velocity accuracy is ±2.5% of reading at 2000 fpm (10 m/s). Flow accuracy depends on velocity and duct size — state duct dimensions when flow is the acceptance metric.

Q: What is the max pressure on the hose ports? A: 10 PSI at each port per OEM published values. Stay within ±4000 Pa measuring range for the published accuracy.

Q: What should I send for a quote? A: Measurement type (ΔP / velocity / flow / temp), expected ranges, duct size if flow, pitot/ToolPak needs, quantity. Compatible with systems using Fluke 922 if you need a drop-in check — we do not claim authorized-dealer status.

Links

ParameterValue
Measuring rangeAir pressure ±4000 Pa (±16 inH2O / ±40 mbar / ±0.6 PSI); air velocity 250–16000 fpm (1–80 m/s); air flow 0–99999 cfm/m3/hr/l/s; temperature 0–50 °C
AccuracyPressure ±1% + 1 Pa (or unit equiv.); velocity ±2.5% of reading at 2000 fpm (10 m/s); temperature ±1% + 2 °C; flow accuracy function of velocity and duct size
OutputHandheld meter display; 99 reading data storage (no analog output)
SupplyFour AA alkaline batteries; typical life 375 h without backlight / 80 h with
Process connectionHose ports for pitot/static; compatible with most pitot tubes (PT12 12 in optional)
ProtectionIP40
Ambient temperatureOperating 0 to +50 °C; storage −40 to +60 °C; RH 0–90% non-condensing
DisplayBright backlit display; Min/Max/Average/Hold
ApprovalsEN61326-1; MIL-PRF-28800F Class 3 (vibration)
MountingHandheld; optional ToolPak magnetic hanging kit
NotesMax pressure at each port 10 PSI. Specs from Fluke 922 datasheet 2791462 D-EN-N Rev C.