E+E Elektronik

E+E EE650 Air Velocity Transmitter

SKU · 43247 · EE650 Air Velocity Transmitter · Brand: E+E Elektronik
Available
Quote on request
No online payment · add lines to RFQ BOM

EE650: HVAC air velocity; 0…10/15/20 m/s; 4–20 mA/0–10 V; Modbus. RFQ.

Download datasheet PDF

RFQ cart holds BOM lines only. Submit for engineering quote.

Key parameters

Measuring range
Selectable 0...10 / 15 / 20 m/s (0...2000 / 3000 / 4000 ft/min); factory 0...20 m/s
Accuracy
+/-(0.2 m/s + 3% of measured value) from 0.2 m/s at 20 C, 45 %RH, 1013 hPa
Type
E+E Elektronik EE650 HVAC air velocity transmitter (thermal anemometer thin-film sensing element)
Response Time
t90 typically 4 s factory; selectable down to 1 s (analogue)
Analogue Output
4-20 mA (3-wire factory) or 0-10 V via jumpers
Digital Interface
RS485 Modbus RTU (9600/19200/38400 baud)
Download datasheet PDF

Fits HVAC duct air-velocity sensing where you need an E+E Elektronik EE650—thermal thin-film air velocity transmitter with selectable 0…10 / 15 / 20 m/s spans, accuracy ±(0.2 m/s + 3% of measured value) from 0.2 m/s, and 4–20 mA or 0–10 V plus RS485 Modbus RTU.

Key advantages

  • Spans — Selectable 0…10 / 15 / 20 m/s
  • Accuracy — ±(0.2 m/s + 3% of m.v.) from 0.2 m/s
  • Outputs — 4–20 mA or 0–10 V; RS485 Modbus RTU
  • Enclosure — IP65 / NEMA 4X polycarbonate
  • Mount — Duct mount or remote probe

Typical applications

  • AHU duct velocity.
  • VAV monitoring.
  • HVAC BMS airspeed.

Selection guide

  • Span jumper
  • Duct vs remote
  • Analogue vs Modbus

Common mistakes

  • Probe in turbulent dead zones.
  • Wrong power class.
  • Ignoring orientation.

When to RFQ / what to tell us

  1. Mount/output/span.
  2. Quantity, ship-to.

Request a Quote · Get selection help

Specs

SpecValue
SKU43247
BrandE+E Elektronik
ModelEE650 Air Velocity Transmitter
Product typeAir Velocity Transmitter
TypeE+E Elektronik EE650 HVAC air velocity transmitter (thermal anemometer thin-film sensing element)
Measuring rangeSelectable 0...10 / 15 / 20 m/s (0...2000 / 3000 / 4000 ft/min); factory 0...20 m/s
Accuracy+/-(0.2 m/s + 3% of measured value) from 0.2 m/s at 20 C, 45 %RH, 1013 hPa
Response timet90 typically 4 s factory; selectable down to 1 s (analogue)
Analogue output4-20 mA (3-wire factory) or 0-10 V via jumpers
Digital interfaceRS485 Modbus RTU (9600/19200/38400 baud)
Power supply24 V AC/DC +/-20% (Class III; Class 2 in USA/Canada)
EnclosureIP65 / NEMA 4X polycarbonate; duct mount or remote probe

Documents

FAQ

Q: Spans? A: 0…10 / 15 / 20 m/s selectable.

Q: Outputs? A: 4–20 mA or 0–10 V; Modbus RTU.

Q: What should I send for a quote? A: Mount/output/span, quantity, ship-to.

Links

ParameterValue
Measuring rangeSelectable 0...10 / 15 / 20 m/s (0...2000 / 3000 / 4000 ft/min); factory 0...20 m/s
Accuracy+/-(0.2 m/s + 3% of measured value) from 0.2 m/s at 20 C, 45 %RH, 1013 hPa
TypeE+E Elektronik EE650 HVAC air velocity transmitter (thermal anemometer thin-film sensing element)
Response Timet90 typically 4 s factory; selectable down to 1 s (analogue)
Analogue Output4-20 mA (3-wire factory) or 0-10 V via jumpers
Digital InterfaceRS485 Modbus RTU (9600/19200/38400 baud)
Power Supply24 V AC/DC +/-20% (Class III; Class 2 in USA/Canada)
EnclosureIP65 / NEMA 4X polycarbonate; duct mount or remote probe
Probe TemperatureProbe -25...+50 C; electronics -10...+50 C
DocumentE+E datasheet EE650 + BA_EE650 operating instructions (epluse.com)