Endress+Hauser

Endress+Hauser RLN22 Isolating Amplifier

SKU · 141049 · RLN22 · Brand: Endress+Hauser
Available
Quote on request
No online payment · add lines to RFQ BOM

NAMUR isolating amplifier, 1-/2-channel relay out, 19.2–30 V DC, DIN 12.5 mm, SIL 2. RFQ + selection help.

Download datasheet PDF

RFQ cart holds BOM lines only. Submit for engineering quote.

Key parameters

Supply
19.2–30 V DC
Ambient temperature
–40…+60 °C (see TI environmental table)
Approvals
CE; SIL
Notes
Technical Information TI01560K. Related SIL document FY01035 for RLN22/RLN42 family.
Function
1-/2-channel NAMUR isolating amplifier with relay output
Input
NAMUR (EN60947-5-6) proximity sensors / open contacts / resistive coupling; thresholds <1.2 mA / >2.1 mA class
Download datasheet PDF

Fits NAMUR (EN60947-5-6) proximity, open-contact, or resistive-coupling loops that need a 1- or 2-channel isolating amplifier with relay output, three-way galvanic isolation, and DIN-rail mounting at 12.5 mm width.

Key advantages

  • NAMUR isolating amplifier — 1-/2-channel for NAMUR proximity sensors and contacts.
  • Relay outputs — changeover (1-ch) or N/O per channel (2-ch) per TI.
  • Three-way galvanic isolation — separates sensor, output, and supply domains.
  • Line-fault monitoring — published LF detection with 19.2–30 V DC supply.

Typical applications

  • Cabinet isolation of NAMUR proximity switches from PLC relay inputs.
  • Hazardous-area sensor loops needing galvanic isolation and LF monitoring.
  • 1- vs 2-channel density choices on DIN rail.

Selection guide

  • Function — 1-/2-channel NAMUR isolating amplifier with relay output.
  • Input — NAMUR (EN60947-5-6) proximity sensors / open contacts / resistive coupling; thresholds <1.2 mA / >2.1 mA class.
  • Output — Relay output (1-ch changeover; 2-ch N/O per channel — verify TI).
  • Supply — 19.2–30 V DC.
  • Isolation — Three-way galvanic isolation.
  • Line-fault monitoring — Yes (per TI).
  • Housing / mount — DIN rail, width 12.5 mm.
  • Ambient — –40…+60 °C (see TI environmental table).
  • SIL — SIL 2 suitability (see FY01035).
  • Approvals — CE; SIL.

Common mistakes

  • Ordering channel count wrong — 1-ch changeover vs 2-ch N/O per channel; verify the TI wiring table before the order code.
  • Assuming every unit is SIL-ready for your safety loop without checking FY01035 and the ordered configuration.
  • Feeding AC supply — this SKU is specified for 19.2–30 V DC only.
  • Ignoring line-fault monitoring wiring/config when the plant expects open-wire / short detection.
  • Confusing RLN22 (NAMUR → relay) with active 0/4–20 mA barriers such as RN42 / RN22.
  • Accessories · Accessories buying guide

When to RFQ / what to tell us

  1. Channel count (1 or 2) and sensor type (NAMUR proximity / open contact / resistive).
  2. Available DC supply (must fit 19.2–30 V DC).
  3. Whether line-fault monitoring must be enabled and how it is wired to the DCS/PLC.
  4. SIL 2 / safety-loop needs and any additional marks required.
  5. Quantity and ship-to country.

Request a Quote · Get selection help

Specs

SpecValue
SKU141049
BrandEndress+Hauser
ModelRLN22
Product typebarrier (NAMUR isolating amplifier)
Function1-/2-channel NAMUR isolating amplifier with relay output
InputNAMUR (EN60947-5-6) proximity / open contacts / resistive; thresholds <1.2 mA / >2.1 mA class
OutputRelay (1-ch changeover; 2-ch N/O per channel — verify TI)
Supply voltage19.2–30 V DC
IsolationThree-way galvanic isolation
Line-fault monitoringYes (per TI)
Housing / mountDIN rail, width 12.5 mm
Ambient temperature–40…+60 °C (see TI environmental table)
SILSIL 2 suitability (see FY01035)
ApprovalsCE; SIL
NotesSpecs from Endress+Hauser TI01560K. Related SIL document FY01035 for RLN22/RLN42 family.

Documents

FAQ

Q: What inputs does the RLN22 accept? A: NAMUR (EN60947-5-6) proximity sensors, open contacts, or resistive coupling, with thresholds in the <1.2 mA / >2.1 mA class per the TI.

Q: Is SIL 2 included? A: OEM documentation lists SIL 2 suitability; confirm against FY01035 and the ordered configuration before claiming it on a safety loop.

Q: What supply does it need? A: 19.2–30 V DC. State available panel DC in the RFQ.

Q: What should I send for a quote? A: Channel count, sensor type, supply, line-fault monitoring need, SIL/marks, quantity, ship-to. Compatible with systems using Endress+Hauser RLN22 if you need a drop-in check — we do not claim authorized-dealer status.

Links

ParameterValue
Supply19.2–30 V DC
Ambient temperature–40…+60 °C (see TI environmental table)
ApprovalsCE; SIL
NotesTechnical Information TI01560K. Related SIL document FY01035 for RLN22/RLN42 family.
Function1-/2-channel NAMUR isolating amplifier with relay output
InputNAMUR (EN60947-5-6) proximity sensors / open contacts / resistive coupling; thresholds <1.2 mA / >2.1 mA class
IsolationThree-way galvanic isolation
Line Fault MonitoringYes (per TI)
HousingDIN rail, width 12.5 mm
SilSIL 2 suitability (see FY01035)