Image unavailable
Image unavailable
AEMC
AEMC Model 607 Power Clamp Meter
Quote on request
No online payment · add lines to RFQ BOM
607: 2000 A AC / 3000 A DC; 1000 V; BT DataView; IP54; >350 h. RFQ.
Download datasheet PDF
RFQ cart holds BOM lines only. Submit for engineering quote.
Key parameters
Measuring range
Current 2000 A AC / 3000 A DC; Voltage 1000 V AC/DC / AC+DC; Resistance to 100 kΩ; Frequency to 20 kHz (V) / 1 kHz (A); Power to 2 MW AC / 3 MW DC
Accuracy
Typical V 1% ± 3 cts; Typical A 1% ± 3 cts (per AEMC Model 607 datasheet)
Output
Bluetooth wireless to DataView PC software (no analog process output)
Supply
4× 1.5 V AA; battery life >350 h
Protection
IP54
Ambient temperature
Operating −4 to 131 °F (−20 to 55 °C)
Fits high-current electrical surveys where you need an AEMC Model 607—current to 2000 A AC / 3000 A DC, voltage to 1000 V AC/DC, resistance to 100 kΩ, and Bluetooth wireless to DataView software with IP54 and >350 h battery life.
Key advantages
- Current — 2000 A AC / 3000 A DC
- Voltage — 1000 V AC/DC / AC+DC
- Accuracy — Typical V/A about 1% ± 3 cts (per datasheet bands)
- Comms — Bluetooth to DataView
- Package — IP54; 4× AA; >350 h
Typical applications
- Industrial load surveys.
- DC / AC plant current checks.
- Logged electrical maintenance.
Selection guide
- Clamp jaw size need
- DataView license/PC
- Spare AA cells
Common mistakes
- Exceeding CAT rating.
- Clamping multiple conductors for current.
- Ignoring Bluetooth pairing setup.
When to RFQ / what to tell us
- Quantity, accessories.
- Ship-to.
Request a Quote · Get selection help
Specs
| Spec | Value |
|---|---|
| SKU | 38041 |
| Brand | AEMC |
| Model | Model 607 |
| Product type | Clamp Meter |
| Measuring range | Current 2000 A AC / 3000 A DC; Voltage 1000 V AC/DC / AC+DC; Resistance to 100 kΩ; Frequency to 20 kHz (V) / 1 kHz (A); Power to 2 MW AC / 3 MW DC |
| Accuracy | Typical V 1% ± 3 cts; Typical A 1% ± 3 cts (per AEMC Model 607 datasheet) |
| Output signal | Bluetooth wireless to DataView PC software (no analog process output) |
| Supply voltage | 4× 1.5 V AA; battery life >350 h |
| IP rating | IP54 |
| Ambient temperature | Operating −4 to 131 °F (−20 to 55 °C) |
Documents
FAQ
Q: Max current? A: 2000 A AC / 3000 A DC.
Q: Software? A: Bluetooth wireless to DataView.
Q: What should I send for a quote? A: Quantity, ship-to.
Links
| Parameter | Value |
|---|---|
| Measuring range | Current 2000 A AC / 3000 A DC; Voltage 1000 V AC/DC / AC+DC; Resistance to 100 kΩ; Frequency to 20 kHz (V) / 1 kHz (A); Power to 2 MW AC / 3 MW DC |
| Accuracy | Typical V 1% ± 3 cts; Typical A 1% ± 3 cts (per AEMC Model 607 datasheet) |
| Output | Bluetooth wireless to DataView PC software (no analog process output) |
| Supply | 4× 1.5 V AA; battery life >350 h |
| Protection | IP54 |
| Ambient temperature | Operating −4 to 131 °F (−20 to 55 °C) |
| Display | 10,000-count blue electroluminescent backlit LCD |
| Approvals | CE; EN/IEC 61010 CAT IV 1000 V |
| Mounting | Handheld; jaw opening 2.36 in (60 mm) |
| Sensor type | TRMS clamp-on power meter with Hall/current transformer jaws |
| Notes | Cat. #2139.61 Power Clamp-On Meter Model 607. Specs from aemc.com Model 607 datasheet 2139-61.pdf. |
| Jaw Opening | 2.36 in (60 mm) |
| Harmonics | Individual harmonics to 25th; THD-r / THD-f |