Rosemount

Rosemount PowerVUE 6x10 Fan/Damper Actuator

SKU · 42115 · PowerVUE 6x10 · Brand: Rosemount
Available
Quote on request
No online payment · add lines to RFQ BOM

Rosemount PowerVUE 6×10: floor-mount torque actuator; ~1800 ft-lb stall; DVC HART/FF. RFQ.

Download datasheet PDF

RFQ cart holds BOM lines only. Submit for engineering quote.

Key parameters

Notes
Features/ordering from Emerson PowerVUE PDS 102-222.A01 PVD 610 section; stall/friction/time cross-checked to Emerson Hagan 6×10 torque family (same actuator construction stated in PowerVUE PDS).
Positioner Type
Rosemount PowerVUE PVD 610 — 6×10 torque-type floor-mounted fan/damper actuator (Hagan pneumatic drive + Fisher FieldVUE DVC6000)
Output Motion
80° shaft rotation (torque-type floor mount); family stroke class 6×10
Stall Torque
Family PowerVUE torque span up to 4,600 ft-lb; 6×10 Hagan-class stall ~1800 ft-lb (2441 N·m) at recommended 100 psig (same Hagan actuator construction cited in PowerVUE PDS)
Max Friction Load
Per Emerson Hagan 6×10 family literature ~450 ft-lb (610 N·m) class
Repeatability
Better than ±0.5% (PowerVUE PDS feature)
Download datasheet PDF

Fits floor-mounted fan/damper torque actuation where you need a Rosemount PowerVUE 6×10 (PVD 610). Torque-type actuator combining Hagan pneumatic drive with Fisher FieldVUE DVC6000, 80° shaft rotation, Hagan-class stall about 1800 ft-lb (2441 N·m) at recommended 100 psig, max friction load about 450 ft-lb class, repeatability better than ±0.5%, full stroke about 5 s or less unloaded, and 4–20 mA HART or FOUNDATION fieldbus input via DVC6000 with plant air 45–100 psig class.

Key advantages

  • Stroke — 80° torque-type floor mount
  • Stall — ~1800 ft-lb at 100 psig class
  • Repeatability — Better than ±0.5%
  • Input — 4–20 mA HART / FF via DVC6000
  • Air — 45–100 psig operating class

Typical applications

  • Fan/damper positioning.
  • Boiler/air heater drives.
  • Floor-mount torque actuators.

Selection guide

  • Torque vs load
  • DVC protocol
  • Air supply quality

Common mistakes

  • Undersized stall torque.
  • Air supply outside 45–100 psig.
  • Ignoring friction load class.

When to RFQ / what to tell us

  1. Torque/protocol/options.
  2. Quantity, ship-to.

Request a Quote · Get selection help

Specs

SpecValue
SKU42115
BrandRosemount
ModelPowerVUE 6x10
Product typeFan/Damper Actuator
Positioner typeRosemount PowerVUE PVD 610 — 6×10 torque-type floor-mounted fan/damper actuator (Hagan pneumatic drive + Fisher FieldVUE DVC6000)
Output motion80° shaft rotation (torque-type floor mount); family stroke class 6×10
Stall torqueFamily PowerVUE torque span up to 4,600 ft-lb; 6×10 Hagan-class stall ~1800 ft-lb (2441 N·m) at recommended 100 psig (same Hagan actuator construction cited in PowerVUE PDS)
Max friction loadPer Emerson Hagan 6×10 family literature ~450 ft-lb (610 N·m) class
RepeatabilityBetter than ±0.5% (PowerVUE PDS feature)
Full stroke timePer Emerson Hagan 6×10 family ~5 s or less unloaded
Input signalDirect 4–20 mA with HART or FOUNDATION fieldbus via DVC6000
Air supplyPlant air via included filter/regulator (Style 4505C21G03); PowerVUE family 45–100 psig operating class

Documents

FAQ

Q: Motion? A: 80° shaft rotation.

Q: Stall class? A: ~1800 ft-lb at 100 psig.

Q: What should I send for a quote? A: Torque/protocol/options, quantity, ship-to.

Links

ParameterValue
NotesFeatures/ordering from Emerson PowerVUE PDS 102-222.A01 PVD 610 section; stall/friction/time cross-checked to Emerson Hagan 6×10 torque family (same actuator construction stated in PowerVUE PDS).
Positioner TypeRosemount PowerVUE PVD 610 — 6×10 torque-type floor-mounted fan/damper actuator (Hagan pneumatic drive + Fisher FieldVUE DVC6000)
Output Motion80° shaft rotation (torque-type floor mount); family stroke class 6×10
Stall TorqueFamily PowerVUE torque span up to 4,600 ft-lb; 6×10 Hagan-class stall ~1800 ft-lb (2441 N·m) at recommended 100 psig (same Hagan actuator construction cited in PowerVUE PDS)
Max Friction LoadPer Emerson Hagan 6×10 family literature ~450 ft-lb (610 N·m) class
RepeatabilityBetter than ±0.5% (PowerVUE PDS feature)
Full Stroke TimePer Emerson Hagan 6×10 family ~5 s or less unloaded
Input SignalDirect 4–20 mA with HART or FOUNDATION fieldbus via DVC6000
Air SupplyPlant air via included filter/regulator (Style 4505C21G03); PowerVUE family 45–100 psig operating class
Air ConsumptionPer Emerson Hagan 6×10 family ~1 scfm free air class
Temperature LimitDVC6000 operating ambient −40 to +85 °C (−40 to +185 °F) per PowerVUE PDS DVC section; actuator heater option 115 VAC 150 W
Unit WeightShipping weight 275 lb / 125 kg (PowerVUE PDS ordering notes)
OptionsManual lock, mechanical air lock, 2× SPDT limit switches, digital EPT (HART), heater/thermostat