Rosemount PowerVUE 6x10 Fan/Damper Actuator
Rosemount PowerVUE 6×10: floor-mount torque actuator; ~1800 ft-lb stall; DVC HART/FF. RFQ.
RFQ cart holds BOM lines only. Submit for engineering quote.
Key parameters
Fits floor-mounted fan/damper torque actuation where you need a Rosemount PowerVUE 6×10 (PVD 610). Torque-type actuator combining Hagan pneumatic drive with Fisher FieldVUE DVC6000, 80° shaft rotation, Hagan-class stall about 1800 ft-lb (2441 N·m) at recommended 100 psig, max friction load about 450 ft-lb class, repeatability better than ±0.5%, full stroke about 5 s or less unloaded, and 4–20 mA HART or FOUNDATION fieldbus input via DVC6000 with plant air 45–100 psig class.
Key advantages
- Stroke — 80° torque-type floor mount
- Stall — ~1800 ft-lb at 100 psig class
- Repeatability — Better than ±0.5%
- Input — 4–20 mA HART / FF via DVC6000
- Air — 45–100 psig operating class
Typical applications
- Fan/damper positioning.
- Boiler/air heater drives.
- Floor-mount torque actuators.
Selection guide
- Torque vs load
- DVC protocol
- Air supply quality
Common mistakes
- Undersized stall torque.
- Air supply outside 45–100 psig.
- Ignoring friction load class.
When to RFQ / what to tell us
- Torque/protocol/options.
- Quantity, ship-to.
Request a Quote · Get selection help
Specs
| Spec | Value |
|---|---|
| SKU | 42115 |
| Brand | Rosemount |
| Model | PowerVUE 6x10 |
| Product type | Fan/Damper Actuator |
| Positioner type | Rosemount PowerVUE PVD 610 — 6×10 torque-type floor-mounted fan/damper actuator (Hagan pneumatic drive + Fisher FieldVUE DVC6000) |
| Output motion | 80° shaft rotation (torque-type floor mount); family stroke class 6×10 |
| Stall torque | Family PowerVUE torque span up to 4,600 ft-lb; 6×10 Hagan-class stall ~1800 ft-lb (2441 N·m) at recommended 100 psig (same Hagan actuator construction cited in PowerVUE PDS) |
| Max friction load | Per Emerson Hagan 6×10 family literature ~450 ft-lb (610 N·m) class |
| Repeatability | Better than ±0.5% (PowerVUE PDS feature) |
| Full stroke time | Per Emerson Hagan 6×10 family ~5 s or less unloaded |
| Input signal | Direct 4–20 mA with HART or FOUNDATION fieldbus via DVC6000 |
| Air supply | Plant air via included filter/regulator (Style 4505C21G03); PowerVUE family 45–100 psig operating class |
Documents
FAQ
Q: Motion? A: 80° shaft rotation.
Q: Stall class? A: ~1800 ft-lb at 100 psig.
Q: What should I send for a quote? A: Torque/protocol/options, quantity, ship-to.
Links
| Parameter | Value |
|---|---|
| Notes | Features/ordering from Emerson PowerVUE PDS 102-222.A01 PVD 610 section; stall/friction/time cross-checked to Emerson Hagan 6×10 torque family (same actuator construction stated in PowerVUE PDS). |
| Positioner Type | Rosemount PowerVUE PVD 610 — 6×10 torque-type floor-mounted fan/damper actuator (Hagan pneumatic drive + Fisher FieldVUE DVC6000) |
| Output Motion | 80° shaft rotation (torque-type floor mount); family stroke class 6×10 |
| Stall Torque | Family PowerVUE torque span up to 4,600 ft-lb; 6×10 Hagan-class stall ~1800 ft-lb (2441 N·m) at recommended 100 psig (same Hagan actuator construction cited in PowerVUE PDS) |
| Max Friction Load | Per Emerson Hagan 6×10 family literature ~450 ft-lb (610 N·m) class |
| Repeatability | Better than ±0.5% (PowerVUE PDS feature) |
| Full Stroke Time | Per Emerson Hagan 6×10 family ~5 s or less unloaded |
| Input Signal | Direct 4–20 mA with HART or FOUNDATION fieldbus via DVC6000 |
| Air Supply | Plant air via included filter/regulator (Style 4505C21G03); PowerVUE family 45–100 psig operating class |
| Air Consumption | Per Emerson Hagan 6×10 family ~1 scfm free air class |
| Temperature Limit | DVC6000 operating ambient −40 to +85 °C (−40 to +185 °F) per PowerVUE PDS DVC section; actuator heater option 115 VAC 150 W |
| Unit Weight | Shipping weight 275 lb / 125 kg (PowerVUE PDS ordering notes) |
| Options | Manual lock, mechanical air lock, 2× SPDT limit switches, digital EPT (HART), heater/thermostat |