Rosemount

Rosemount PowerVUE 8x14 Fan/Damper Actuator

SKU · 42116 · PowerVUE 8x14 · Brand: Rosemount
Available
Quote on request
No online payment · add lines to RFQ BOM

Rosemount PowerVUE 8×14: floor-mount torque actuator; family to 4600 ft-lb; DVC HART/FF. RFQ.

Download datasheet PDF

RFQ cart holds BOM lines only. Submit for engineering quote.

Key parameters

Notes
Ordering/features from Emerson PowerVUE PDS 102-222.A01 PVD814 section; stall/friction/time aligned to Emerson Hagan 8×14 torque family (same actuator construction).
Positioner Type
Rosemount PowerVUE PVD814 — 8×14 torque-type floor-mounted fan/damper actuator (Hagan pneumatic drive + Fisher FieldVUE DVC)
Output Motion
80° shaft rotation (torque-type floor mount); family stroke class 8×14
Stall Torque
PowerVUE family upper torque 4,600 ft-lb (6238 N·m) class at recommended 100 psig (PDS intro + Emerson Hagan 8×14 family)
Max Friction Load
Per Emerson Hagan 8×14 family ~1100 ft-lb (1492 N·m) class
Repeatability
Better than ±0.5% (PowerVUE PDS feature set)
Download datasheet PDF

Fits larger floor-mounted fan/damper torque actuation where you need a Rosemount PowerVUE 8×14 (PVD814). Torque-type actuator with Hagan pneumatic drive and Fisher FieldVUE DVC, 80° shaft rotation, PowerVUE family upper torque 4,600 ft-lb (6238 N·m) class at recommended 100 psig, max friction load about 1100 ft-lb class, repeatability better than ±0.5%, full stroke about 2.5 s unloaded class, and 4–20 mA HART or FOUNDATION fieldbus via DVC5000/6000 with plant air 45–100 psig class.

Key advantages

  • Stroke — 80° torque-type floor mount
  • Torque class — Family to 4,600 ft-lb
  • Friction — ~1100 ft-lb class
  • Repeatability — Better than ±0.5%
  • Input — 4–20 mA HART / FF via DVC

Typical applications

  • Large fan/damper drives.
  • High-torque air heater actuation.
  • Floor-mount PowerVUE packages.

Selection guide

  • Torque vs load
  • DVC series
  • Air supply

Common mistakes

  • Confusing 6×10 vs 8×14 torque.
  • Air supply outside class.
  • Ignoring friction load.

When to RFQ / what to tell us

  1. Torque/protocol/options.
  2. Quantity, ship-to.

Request a Quote · Get selection help

Specs

SpecValue
SKU42116
BrandRosemount
ModelPowerVUE 8x14
Product typeFan/Damper Actuator
Positioner typeRosemount PowerVUE PVD814 — 8×14 torque-type floor-mounted fan/damper actuator (Hagan pneumatic drive + Fisher FieldVUE DVC)
Output motion80° shaft rotation (torque-type floor mount); family stroke class 8×14
Stall torquePowerVUE family upper torque 4,600 ft-lb (6238 N·m) class at recommended 100 psig (PDS intro + Emerson Hagan 8×14 family)
Max friction loadPer Emerson Hagan 8×14 family ~1100 ft-lb (1492 N·m) class
RepeatabilityBetter than ±0.5% (PowerVUE PDS feature set)
Full stroke timePer Emerson Hagan 8×14 family ~2.5 s unloaded class
Input signal4–20 mA HART or FOUNDATION fieldbus via DVC5000/6000
Air supplyPlant air via included filter/regulator Style 4505C21G03; PowerVUE family 45–100 psig operating class

Documents

FAQ

Q: Family torque? A: Up to 4,600 ft-lb class.

Q: Stroke time class? A: ~2.5 s unloaded.

Q: What should I send for a quote? A: Torque/protocol/options, quantity, ship-to.

Links

ParameterValue
NotesOrdering/features from Emerson PowerVUE PDS 102-222.A01 PVD814 section; stall/friction/time aligned to Emerson Hagan 8×14 torque family (same actuator construction).
Positioner TypeRosemount PowerVUE PVD814 — 8×14 torque-type floor-mounted fan/damper actuator (Hagan pneumatic drive + Fisher FieldVUE DVC)
Output Motion80° shaft rotation (torque-type floor mount); family stroke class 8×14
Stall TorquePowerVUE family upper torque 4,600 ft-lb (6238 N·m) class at recommended 100 psig (PDS intro + Emerson Hagan 8×14 family)
Max Friction LoadPer Emerson Hagan 8×14 family ~1100 ft-lb (1492 N·m) class
RepeatabilityBetter than ±0.5% (PowerVUE PDS feature set)
Full Stroke TimePer Emerson Hagan 8×14 family ~2.5 s unloaded class
Input Signal4–20 mA HART or FOUNDATION fieldbus via DVC5000/6000
Air SupplyPlant air via included filter/regulator Style 4505C21G03; PowerVUE family 45–100 psig operating class
Air ConsumptionPer Emerson Hagan 8×14 family ~2 scfm steady-state class
Temperature LimitDVC ambient −40 to +85 °C per PowerVUE PDS; optional heater/thermostat 115 VAC 150 W (not for hazardous areas)
Unit WeightShipping weight 550 lb / 249 kg (PowerVUE PDS ordering notes)
OptionsMechanical air lock, 2× SPDT limit switches, digital EPT + 2 contacts (HART), heater