Rosemount PowerVUE 8x14 Fan/Damper Actuator
Rosemount PowerVUE 8×14: floor-mount torque actuator; family to 4600 ft-lb; DVC HART/FF. RFQ.
RFQ cart holds BOM lines only. Submit for engineering quote.
Key parameters
Fits larger floor-mounted fan/damper torque actuation where you need a Rosemount PowerVUE 8×14 (PVD814). Torque-type actuator with Hagan pneumatic drive and Fisher FieldVUE DVC, 80° shaft rotation, PowerVUE family upper torque 4,600 ft-lb (6238 N·m) class at recommended 100 psig, max friction load about 1100 ft-lb class, repeatability better than ±0.5%, full stroke about 2.5 s unloaded class, and 4–20 mA HART or FOUNDATION fieldbus via DVC5000/6000 with plant air 45–100 psig class.
Key advantages
- Stroke — 80° torque-type floor mount
- Torque class — Family to 4,600 ft-lb
- Friction — ~1100 ft-lb class
- Repeatability — Better than ±0.5%
- Input — 4–20 mA HART / FF via DVC
Typical applications
- Large fan/damper drives.
- High-torque air heater actuation.
- Floor-mount PowerVUE packages.
Selection guide
- Torque vs load
- DVC series
- Air supply
Common mistakes
- Confusing 6×10 vs 8×14 torque.
- Air supply outside class.
- Ignoring friction load.
When to RFQ / what to tell us
- Torque/protocol/options.
- Quantity, ship-to.
Request a Quote · Get selection help
Specs
| Spec | Value |
|---|---|
| SKU | 42116 |
| Brand | Rosemount |
| Model | PowerVUE 8x14 |
| Product type | Fan/Damper Actuator |
| Positioner type | Rosemount PowerVUE PVD814 — 8×14 torque-type floor-mounted fan/damper actuator (Hagan pneumatic drive + Fisher FieldVUE DVC) |
| Output motion | 80° shaft rotation (torque-type floor mount); family stroke class 8×14 |
| Stall torque | PowerVUE family upper torque 4,600 ft-lb (6238 N·m) class at recommended 100 psig (PDS intro + Emerson Hagan 8×14 family) |
| Max friction load | Per Emerson Hagan 8×14 family ~1100 ft-lb (1492 N·m) class |
| Repeatability | Better than ±0.5% (PowerVUE PDS feature set) |
| Full stroke time | Per Emerson Hagan 8×14 family ~2.5 s unloaded class |
| Input signal | 4–20 mA HART or FOUNDATION fieldbus via DVC5000/6000 |
| Air supply | Plant air via included filter/regulator Style 4505C21G03; PowerVUE family 45–100 psig operating class |
Documents
FAQ
Q: Family torque? A: Up to 4,600 ft-lb class.
Q: Stroke time class? A: ~2.5 s unloaded.
Q: What should I send for a quote? A: Torque/protocol/options, quantity, ship-to.
Links
| Parameter | Value |
|---|---|
| Notes | Ordering/features from Emerson PowerVUE PDS 102-222.A01 PVD814 section; stall/friction/time aligned to Emerson Hagan 8×14 torque family (same actuator construction). |
| Positioner Type | Rosemount PowerVUE PVD814 — 8×14 torque-type floor-mounted fan/damper actuator (Hagan pneumatic drive + Fisher FieldVUE DVC) |
| Output Motion | 80° shaft rotation (torque-type floor mount); family stroke class 8×14 |
| Stall Torque | PowerVUE family upper torque 4,600 ft-lb (6238 N·m) class at recommended 100 psig (PDS intro + Emerson Hagan 8×14 family) |
| Max Friction Load | Per Emerson Hagan 8×14 family ~1100 ft-lb (1492 N·m) class |
| Repeatability | Better than ±0.5% (PowerVUE PDS feature set) |
| Full Stroke Time | Per Emerson Hagan 8×14 family ~2.5 s unloaded class |
| Input Signal | 4–20 mA HART or FOUNDATION fieldbus via DVC5000/6000 |
| Air Supply | Plant air via included filter/regulator Style 4505C21G03; PowerVUE family 45–100 psig operating class |
| Air Consumption | Per Emerson Hagan 8×14 family ~2 scfm steady-state class |
| Temperature Limit | DVC ambient −40 to +85 °C per PowerVUE PDS; optional heater/thermostat 115 VAC 150 W (not for hazardous areas) |
| Unit Weight | Shipping weight 550 lb / 249 kg (PowerVUE PDS ordering notes) |
| Options | Mechanical air lock, 2× SPDT limit switches, digital EPT + 2 contacts (HART), heater |