Honeywell

Honeywell FS10-R Fire Sentry

SKU · 103756 · FS10-R Fire Sentry System · Brand: Honeywell
Available
Quote on request
No online payment · add lines to RFQ BOM

Multi-spectral IR flame detector for paint booths. Staged ALERT/alarm. RFQ + engineer selection help.

Download datasheet PDF

RFQ cart holds BOM lines only. Submit for engineering quote.

Key parameters

Approvals
FM; CE; Class I Div 1&2 Groups B,C,D; Class II Div 1&2 Groups E,F,G; Class III
Detection Technology
Multi-spectral digital electro-optical IR (Visible + Near-band IR + Wide-band IR)
Application
Electrostatic liquid/powder paint spray booths; NFPA 33 oriented Fire Sentry FS System 10 family
Response Time
ALERT 0.3 s (fireball); Fire Early Warning 1 s; Fire Alarm <5 s if fire continues
Field Of View
90° (±45° H/V)
Spectral Sensitivity
Visible 400–700 nm; Near Band IR 0.7–1.1 µm; Wide Band IR 0.7–3.5 µm
Download datasheet PDF

Fits electrostatic paint-spray booths where you need a Honeywell FS10-R multi-spectral IR Fire Sentry detector with ALERT / early-alert / alarm stages.

Key advantages

  • Multi-spectral IR — Multi-spectral digital electro-optical IR (Visible + Near-band IR + Wide-band IR)
  • Booth-oriented — Electrostatic liquid/powder paint spray booths; NFPA 33 oriented Fire Sentry FS System 10 family
  • Staged response — ALERT 0.3 s (fireball); Early-alert stage 1 s; Fire Alarm <5 s if fire continues
  • FOV / sensitivity — 90° (±45° H/V); 45 ft and 30 ft to 1 sq ft gasoline fire (per SS01149B)
  • Outputs — Alert / early-alert SPST N.O.; Fire Alarm SPST N.O.; Fault SPST N.O.; 1 A @ 24 VDC; RS-485; through-the-lens self-test.

Typical applications

  • Electrostatic liquid/powder paint spray booth flame detection (NFPA 33 oriented family).
  • Systems needing ALERT / early-alert / fire-alarm relay stages.
  • 24 VDC loops with RS-485 supervision.

Selection guide

  • Sensitivity / distance — 45 ft and 30 ft to 1 sq ft gasoline fire (per SS01149B)
  • FOV — 90° (±45° H/V)
  • Power — 24 VDC nominal (18–32 VDC regulated); consumption Normal ~85 mA; Alarm ~120 mA typical
  • Outputs / comms — Alert / early-alert SPST N.O.; Fire Alarm SPST N.O.; Fault SPST N.O.; 1 A @ 24 VDC; RS-485
  • Self-test — Built-in automatic through-the-lens self-test

Common mistakes

  • Using FS10-R outside spray-booth oriented duties without checking FS20X/FS24X families.
  • Ignoring staged ALERT vs Fire Alarm timing in the suppression logic.
  • Under-sizing 24 VDC supply for alarm current (~120 mA typical).

When to RFQ / what to tell us

  1. Booth type (liquid/powder), fuel of concern, mounting distance.
  2. Relay/RS-485 needs; quantity; ship-to; area classification if any.

Request a Quote · Get selection help

Specs

SpecValue
SKU103756
BrandHoneywell
ModelFS10-R Fire Sentry System
Product typeFlame Detector
DetectionMulti-spectral digital electro-optical IR (Visible + Near-band IR + Wide-band IR)
ApplicationElectrostatic liquid/powder paint spray booths; NFPA 33 oriented Fire Sentry FS System 10 family
Response timeALERT 0.3 s (fireball); Early-alert stage 1 s; Fire Alarm <5 s if fire continues
Field of view90° (±45° H/V)
Spectral sensitivityVisible 400–700 nm; Near Band IR 0.7–1.1 µm; Wide Band IR 0.7–3.5 µm
Sensitivity45 ft and 30 ft to 1 sq ft gasoline fire (per SS01149B)
Input power24 VDC nominal (18–32 VDC regulated)
Power consumptionNormal ~85 mA; Alarm ~120 mA typical
OutputsAlert / early-alert SPST N.O.; Fire Alarm SPST N.O.; Fault SPST N.O.; 1 A @ 24 VDC; RS-485
Self-testBuilt-in automatic through-the-lens self-test

Documents

FAQ

Q: Response times? A: ALERT 0.3 s (fireball); Early-alert stage 1 s; Fire Alarm <5 s if fire continues (OEM).

Q: Spectral bands? A: Visible 400–700 nm; Near Band IR 0.7–1.1 µm; Wide Band IR 0.7–3.5 µm.

Q: What should I send for a quote? A: Duty, distance, outputs, quantity.

Links

ParameterValue
ApprovalsFM; CE; Class I Div 1&2 Groups B,C,D; Class II Div 1&2 Groups E,F,G; Class III
Detection TechnologyMulti-spectral digital electro-optical IR (Visible + Near-band IR + Wide-band IR)
ApplicationElectrostatic liquid/powder paint spray booths; NFPA 33 oriented Fire Sentry FS System 10 family
Response TimeALERT 0.3 s (fireball); Fire Early Warning 1 s; Fire Alarm <5 s if fire continues
Field Of View90° (±45° H/V)
Spectral SensitivityVisible 400–700 nm; Near Band IR 0.7–1.1 µm; Wide Band IR 0.7–3.5 µm
Sensitivity45 ft and 30 ft to 1 sq ft gasoline fire (per SS01149B)
Input Power24 VDC nominal (18–32 VDC regulated)
Power ConsumptionNormal ~85 mA; Alarm ~120 mA typical
OutputsAlert/Early Warning SPST N.O.; Fire Alarm SPST N.O.; Fault SPST N.O.; 1 A @ 24 VDC; RS-485
Self TestBuilt-in automatic through-the-lens self-test
Operating Temperature−40 to +85 °C (−40 to +185 °F); humidity 10–90% RH non-condensing
EnclosureCopper-free powder-coated aluminum or optional 316 SS; NEMA 3/4/4X; two ¾" NPT; ~1.7 kg aluminum
FamilyFire Sentry FS System 10 / FS10-R