Rosemount

Rosemount 975HR Flame Detector

SKU · 43515 · 975HR · Brand: Rosemount
Available
Quote on request
No online payment · add lines to RFQ BOM

Rosemount 975HR: multi-spectrum IR; H2/HC; six sensitivity levels; SIL3-class. RFQ.

Download datasheet PDF

RFQ cart holds BOM lines only. Submit for engineering quote.

Key parameters

Type
Multi-spectrum IR hydrogen flame detector — Rosemount 975HR (QuadSense)
Detection
Hydrocarbon and hydrogen flames; hydrogen to ~164 ft (50 m); hydrocarbons to ~300 ft (90 m)
Response Time
High-speed response under 50 ms
Sensors
Four IR bands (multi-spectrum QuadSense)
Sensitivity Levels
Six selectable sensitivity levels
Operating Temperature
−76 °F (−60 °C) to +185 °F (+85 °C)
Download datasheet PDF

Fits fixed multi-spectrum IR flame detection where you need a Rosemount 975HR. QuadSense four-IR-band detection covers hydrocarbon and hydrogen flames with six selectable sensitivity levels, response under 50 ms, heated window options, and HART / Modbus / relay / 4–20 mA outputs per configuration.

Key advantages

  • Sensors — Four IR bands (multi-spectrum QuadSense)
  • Fuels — Hydrocarbon and hydrogen flames
  • Sensitivity — Six selectable levels
  • Response — Under 50 ms
  • Optics — Heated window options; IR BIT

Typical applications

  • Compressor stations.
  • Hydrogen process units.
  • Tank farm flame detection.

Selection guide

  • Sensitivity
  • Output set
  • Heated optics

Common mistakes

  • Sun/welding false-alarm geometry.
  • Dirty window.
  • Wrong power range.

When to RFQ / what to tell us

  1. RM/options.
  2. Quantity, ship-to.

Request a Quote · Get selection help

Specs

SpecValue
SKU43515
BrandRosemount
Model975HR
Product typeFlame Detector
TypeMulti-spectrum IR hydrogen flame detector — Rosemount 975HR (QuadSense)
DetectionHydrocarbon and hydrogen flames; hydrogen to ~164 ft (50 m); hydrocarbons to ~300 ft (90 m)
Response timeHigh-speed response under 50 ms
SensorsFour IR bands (multi-spectrum QuadSense)
Sensitivity levelsSix selectable sensitivity levels
Operating temperature−76 °F (−60 °C) to +185 °F (+85 °C)
OutputsHART; Modbus RS-485; relays / 4–20 mA (see RM)
OpticsHeated window (two-mode) against condensation/icing; IR BIT

Documents

FAQ

Q: Sensitivity levels? A: Six selectable.

Q: Response? A: Under 50 ms.

Q: What should I send for a quote? A: Options, quantity, ship-to.

Links

ParameterValue
TypeMulti-spectrum IR hydrogen flame detector — Rosemount 975HR (QuadSense)
DetectionHydrocarbon and hydrogen flames; hydrogen to ~164 ft (50 m); hydrocarbons to ~300 ft (90 m)
Response TimeHigh-speed response under 50 ms
SensorsFour IR bands (multi-spectrum QuadSense)
Sensitivity LevelsSix selectable sensitivity levels
Operating Temperature−76 °F (−60 °C) to +185 °F (+85 °C)
OutputsHART; Modbus RS-485; relays / 4–20 mA (see RM)
OpticsHeated window (two-mode) against condensation/icing; IR BIT
ReliabilitySIL3 compatible; ~150,000 hours MTBF (PDS)
DocumentPDS 00813-0200-4976 Rev AE + Manual 00809-1400-4975