Image unavailable
Image unavailable
Alpha Omega Instruments (AOI)
Alpha Omega Instruments Series 1300 Oxygen Deficiency Monitor
Quote on request
No online payment · add lines to RFQ BOM
AOI Series 1300: 0–30% O₂; ±1% FS; to 3 sensors; 4 relays; 90–264 VAC. RFQ.
Download datasheet PDF
RFQ cart holds BOM lines only. Submit for engineering quote.
Key parameters
Accuracy
+/-1% of full scale
Display
4 line x 20 character LCD; built-in audible alarm ~85 dB
Type
Wall-mount oxygen deficiency monitor (Series 1300)
Measurement Range
0-30% oxygen
Response
90% of full scale in less than 20 s
Sensor
Extended-life electrochemical sensor with Enhanced Electrolyte System (EES); up to 3 sensor inputs
Fits area oxygen-deficiency monitoring where you need an Alpha Omega Instruments Series 1300—wall-mount 0–30% oxygen monitor with ±1% of full scale accuracy, response under 20 s to 90% FS, up to three sensor inputs, four SPDT Form C alarm relays, and universal 90–264 VAC power.
Key advantages
- Range — 0–30% oxygen
- Accuracy — ±1% of full scale
- Response — 90% FS in less than 20 s
- Sensors — Up to 3 inputs; EES electrochemical
- Alarms — Four SPDT Form C; ~85 dB audible
Typical applications
- Oxygen deficiency rooms.
- Cryogen / N2 areas.
- Multi-point area O₂.
Selection guide
- Sensor count
- Relay setpoints
- Mount location
Common mistakes
- Sensors in dead air.
- Ignoring audible disable.
- Wrong VAC.
When to RFQ / what to tell us
- Sensor count.
- Quantity, ship-to.
Request a Quote · Get selection help
Specs
| Spec | Value |
|---|---|
| SKU | 45767 |
| Brand | Alpha Omega Instruments |
| Model | AOI Series 1300 Oxygen Analyzer |
| Product type | Oxygen Analyzer |
| Type | Wall-mount oxygen deficiency monitor (Series 1300) |
| Measurement range | 0-30% oxygen |
| Accuracy | +/-1% of full scale |
| Response | 90% of full scale in less than 20 s |
| Sensor | Extended-life electrochemical sensor with Enhanced Electrolyte System (EES); up to 3 sensor inputs |
| Outputs | Two configurable 0-20 / 4-20 mA; RS-232; four SPDT Form C alarm relays |
| Display | 4 line x 20 character LCD; built-in audible alarm ~85 dB |
| Power | Universal 90-264 VAC, 47-63 Hz |
Documents
FAQ
Q: Range? A: 0–30% oxygen.
Q: Sensors? A: Up to 3 inputs.
Q: What should I send for a quote? A: Sensor count, quantity, ship-to.
Links
| Parameter | Value |
|---|---|
| Accuracy | +/-1% of full scale |
| Display | 4 line x 20 character LCD; built-in audible alarm ~85 dB |
| Type | Wall-mount oxygen deficiency monitor (Series 1300) |
| Measurement Range | 0-30% oxygen |
| Response | 90% of full scale in less than 20 s |
| Sensor | Extended-life electrochemical sensor with Enhanced Electrolyte System (EES); up to 3 sensor inputs |
| Outputs | Two configurable 0-20 / 4-20 mA; RS-232; four SPDT Form C alarm relays |
| Power | Universal 90-264 VAC, 47-63 Hz |
| Operating Temp | 10 to 40 C (50 to 104 F); 90% RH max non-condensing |
| Document | Process Insights Series 1300 Datasheet DS_v26 |