VEGA

VEGA VEGATRENN 141 Single Channel Separator

SKU · 582275 · VEGATRENN 141 · Brand: VEGA
Available
Quote on request
No online payment · add lines to RFQ BOM

VEGA VEGATRENN 141: single-channel active Ex separator; 4–20 mA/HART powered. RFQ.

Download datasheet PDF

RFQ cart holds BOM lines only. Submit for engineering quote.

Key parameters

Supply
AC 24…230 V (−15%/+10%) 50/60 Hz; DC 24…65 V (−15%/+10%)
Ambient temperature
−20…+60 °C (−4…+140 °F)
Mounting
DIN rail 35×7.5 mm per EN 50022/60715
Channels
Single channel active Ex separator
Sensor Input
1 × 4…20 mA/HART (up to 5× HART multidrop)
Input Type
Active (sensor powered by VEGATRENN 141)
Download datasheet PDF

Fits Ex-area 4–20 mA/HART separation on a single loop where you need a VEGA VEGATRENN 141. Active single-channel separator that powers the sensor, accepts 4…20 mA/HART (up to five HART multidrop devices), provides 21…16.5 V DC at operating current with 24 V DC off-load, and repeats an active 4…20 mA/HART output under 15.5 V DC off-load.

Key advantages

  • Channels — One active separator
  • HART — Up to 5× multidrop
  • Sensor power — From VEGATRENN 141
  • Terminal V — 21…16.5 V @ 4…20 mA
  • Output — Active 4…20 mA/HART

Typical applications

  • Single Ex transmitter loops.
  • HART separator panels.
  • Active barrier replacements.

Selection guide

  • Approvals
  • Multidrop plan
  • Supply

Common mistakes

  • Assuming passive input.
  • Overloading multidrop.
  • Voltage budget errors.

When to RFQ / what to tell us

  1. Approvals/options.
  2. Quantity, ship-to.

Request a Quote · Get selection help

Specs

SpecValue
SKU582275
BrandVEGA
ModelVEGATRENN 141
Product typeSignal Separator
ChannelsSingle channel active Ex separator
Sensor input1 × 4…20 mA/HART (up to 5× HART multidrop)
Input typeActive (sensor powered by VEGATRENN 141)
Terminal voltage21…16.5 V DC at 4…20 mA; off-load 24 V DC (±1 V)
Output1 × active 4…20 mA/HART; off-load <15.5 V DC

Documents

FAQ

Q: Active? A: Yes — powers the sensor.

Q: Multidrop? A: Up to 5× HART.

Q: What should I send for a quote? A: Approvals/options, quantity, ship-to.

Links

ParameterValue
SupplyAC 24…230 V (−15%/+10%) 50/60 Hz; DC 24…65 V (−15%/+10%)
Ambient temperature−20…+60 °C (−4…+140 °F)
MountingDIN rail 35×7.5 mm per EN 50022/60715
ChannelsSingle channel active Ex separator
Sensor Input1 × 4…20 mA/HART (up to 5× HART multidrop)
Input TypeActive (sensor powered by VEGATRENN 141)
Terminal Voltage21…16.5 V DC at 4…20 mA; off-load 24 V DC (±1 V)
Power ConsumptionMax 3 W (15 VA)
Protection RatingIP20; Protection class II; Pollution degree 2
HartBidirectional HART via front sockets or terminals
SilSIL2 qualification