E+H Liquipoint T FTW31 Level Switch
Conductive multipoint level switch: rods to 4 m, ≥10 µS/cm, IP66. RFQ + selection help.
RFQ cart holds BOM lines only. Submit for engineering quote.
Key parameters
Fits conductive liquid point-level detection where you need multipoint rod probes (to 4 m) or related rope probes (FTW32 to 15 m) with conductivity ≥10 µS/cm and compact electronics inserts (DC-PNP / relay / NAMUR).
Key advantages
- Conductive multipoint detection — Rod probes to 4 m; related FTW32 rope to 15 m; up to 5 switch points.
- ≥10 µS/cm liquids — Conductive point level with FEW52/54/58 inserts or separate FTW325.
- IP66 field package — G 1½ / NPT 1½ connections; 316L / PP / PPS wetted options.
- WHG / ATEX options — Overfill and Ex marks by order code.
Typical applications
- Conductive liquid high/low multipoint detection in tanks.
- Cost-effective conductive probes where vibronic or capacitance is not required.
- Installs needing NAMUR, DC-PNP, or AC/DC relay electronics inserts.
Selection guide
- Measuring range — Multipoint conductive detection; rod probes to 4 m (13 ft); rope probes (FTW32) to 15 m; up to 5 switch points.
- Accuracy — No continuous level accuracy; point switching. Measuring error ±10 % at 100 Ω–100 kΩ / ±5 % at 1–10 kΩ (TI test conditions).
- Output — FEW52 DC-PNP; FEW54 AC/DC relay; FEW58 NAMUR; or separate FTW325 transmitter.
- Supply — FEW52 DC PNP ~10.8…45 V; FEW54 relay 20…230 VAC / 20…55 VDC (per TI electronics); FEW58 NAMUR.
- Process connection — G 1½ / NPT 1½ (housing versions per TI).
- Wetted materials — 316L, PP, PPS.
- IP — IP66.
- Media temperature — −40 to +100 °C (−40 to +212 °F) per process chart (depends on ambient/electronics).
- Ambient — Non-haz −40…70 °C (−40…158 °F); FEW58 NAMUR −40…60 °C; storage −40…80 °C.
- Process pressure — −1 to 10 bar (vacuum…145 psi).
- Min conductivity — ≥10 µS/cm.
- Approvals — WHG; ATEX; EAC Ex; CE.
- Notes — Specs from TI00375F/00/EN/14.16. Conductivity ≥10 µS/cm required.
Common mistakes
- Applying to non-conductive media below 10 µS/cm — conductive principle will not switch reliably.
- Ordering FTW31 rod when tank height needs FTW32 rope (to 15 m).
- Leaving electronics insert blank — FEW52 DC-PNP vs FEW54 relay vs FEW58 NAMUR vs separate FTW325.
- Ignoring process pressure (−1…10 bar) and media temperature (−40…+100 °C) charts vs ambient/electronics derating.
- Expecting continuous level accuracy — this is point switching only.
When to RFQ / what to tell us
- Rod vs rope, probe length, number of switch points (up to 5), and media conductivity.
- Electronics insert (FEW52 / FEW54 / FEW58 / FTW325), process connection (G 1½ / NPT 1½), Ex/WHG needs.
- Quantity, ship-to, wetted material preference (316L / PP / PPS).
Request a Quote · Get selection help
Specs
| Spec | Value |
|---|---|
| SKU | 48491 |
| Brand | Endress+Hauser |
| Model | Liquipoint T FTW31 |
| Product type | level_switch |
| Measuring range | Multipoint conductive detection; rod probes to 4 m; rope probes (FTW32) to 15 m; up to 5 switch points |
| Accuracy | Point switching; measuring error ±10 % at 100 Ω–100 kΩ / ±5 % at 1–10 kΩ (TI test conditions) |
| Output | FEW52 DC-PNP; FEW54 AC/DC relay; FEW58 NAMUR; or separate FTW325 transmitter |
| Supply | FEW52 DC PNP ~10.8…45 V; FEW54 relay 20…230 VAC / 20…55 VDC; FEW58 NAMUR |
| Process connection | G 1½ / NPT 1½ (housing versions per TI) |
| Wetted materials | 316L, PP, PPS |
| IP rating | IP66 |
| Media temperature | −40 to +100 °C (depends on ambient/electronics) |
| Ambient temperature | Non-haz −40…70 °C; FEW58 NAMUR −40…60 °C; storage −40…80 °C |
| Process pressure | −1 to 10 bar |
| Min conductivity | ≥10 µS/cm |
| Approvals | WHG; ATEX; EAC Ex; CE |
| Notes | Specs from TI00375F/00/EN/14.16. Conductivity ≥10 µS/cm required. |
Documents
FAQ
Q: What minimum conductivity is required? A: ≥10 µS/cm.
Q: Rod or rope? A: FTW31 rods to 4 m; related FTW32 rope probes to 15 m — state tank height on the RFQ.
Q: What should I send for a quote? A: Probe type/length, switch points, electronics insert, connection, marks, quantity. Compatible with systems using Endress+Hauser Liquipoint T FTW31 — we do not claim authorized-dealer status.
Links
| Parameter | Value |
|---|---|
| Measuring range | Multipoint conductive detection; rod probes to 4 m (13 ft); rope probes (FTW32) to 15 m; up to 5 switch points |
| Accuracy | No continuous level accuracy; point switching. Measuring error ±10 % at 100 Ω–100 kΩ / ±5 % at 1–10 kΩ (TI test conditions) |
| Output | FEW52 DC-PNP; FEW54 AC/DC relay; FEW58 NAMUR; or separate FTW325 transmitter |
| Supply | FEW52 DC PNP ~10.8…45 V; FEW54 relay 20…230 VAC / 20…55 VDC (per TI electronics); FEW58 NAMUR |
| Process connection | G 1½ / NPT 1½ (housing versions per TI) |
| Wetted parts | 316L, PP, PPS |
| Housing | Field housing with electronic insert options |
| Protection | IP66 |
| Media temperature | −40 to +100 °C (−40 to +212 °F) per process chart (depends on ambient/electronics) |
| Ambient temperature | Non-haz −40…70 °C (−40…158 °F); FEW58 NAMUR −40…60 °C; storage −40…80 °C |
| Display | LED indicators on electronics inserts |
| Communication | DC PNP / relay (no fieldbus on compact inserts) |
| Approvals | WHG; ATEX; EAC Ex; CE |
| Notes | Specs from TI00375F/00/EN/14.16 and US product page. Conductivity ≥10 µS/cm required. |
| Process Pressure | −1 to 10 bar (vacuum…145 psi) |
| Min Conductivity | ≥10 µS/cm |