Rosemount

Rosemount 2051L Level Transmitter

SKU · 24482 · 2051L Level Transmitter · Brand: Rosemount
Available
Quote on request
No online payment · add lines to RFQ BOM

Rosemount 2051L: Hydrostatic level / SG via DP level; Direct Mount and Tuned-System; HART / WirelessHART / FF / PA / low-power. RFQ.

Download datasheet PDF

RFQ cart holds BOM lines only. Submit for engineering quote.

Key parameters

Process connection
Flanged ANSI/ASME, EN/DIN and JIS process connections
Wetted parts
316L SST, Alloy C-276 and Tantalum diaphragm options
Type
Rosemount 2051L liquid level transmitter (DP level with direct-mount / Tuned-System seals)
Measurement
Hydrostatic level and specific gravity measurement using flanged DP level architecture
Pressure
Level ranges up to about 300 psi (20.7 bar) depending on range code
Protocols
4-20 mA HART, WirelessHART, FOUNDATION Fieldbus, PROFIBUS PA, and 1-5 V low-power HART options
Download datasheet PDF

Fits flanged DP liquid level where you need a Rosemount 2051L. Hydrostatic level and specific gravity measurement with Direct Mount / Tuned-System seals, level ranges up to about 300 psi (20.7 bar) by range code, protocols including 4–20 mA HART, WirelessHART, FOUNDATION Fieldbus, PROFIBUS PA and 1–5 V low-power HART, flanged ANSI/ASME / EN/DIN / JIS connections, 316L / Alloy C-276 / Tantalum diaphragms, SIL 2/3 to IEC 61508, and LOI commissioning.

Key advantages

  • Measurement — Hydrostatic level / SG via DP level
  • Seals — Direct Mount and Tuned-System
  • Protocols — HART / WirelessHART / FF / PA / low-power
  • Materials — 316L, Alloy C-276, Tantalum options
  • Safety — SIL 2/3 IEC 61508; NACE / hazloc options

Typical applications

  • Vessel / tank DP level.
  • Specific gravity measurement.
  • Flanged seal level installations.

Selection guide

  • Range code / seal system
  • Protocol
  • Diaphragm material / flange standard

Common mistakes

  • Wrong flange standard.
  • Ignoring SG vs level configuration.
  • Skipping SIL option when required.

When to RFQ / what to tell us

  1. Range, seal, protocol, materials, flange, SIL, quantity, ship-to.

Request a Quote · Get selection help

Specs

SpecValue
SKU24482
BrandRosemount
Model2051L Level Transmitter
Product typeLevel Transmitter
TypeRosemount 2051L liquid level transmitter (DP level with direct-mount / Tuned-System seals)
MeasurementHydrostatic level and specific gravity measurement using flanged DP level architecture
PressureLevel ranges up to about 300 psi (20.7 bar) depending on range code
Protocols4-20 mA HART, WirelessHART, FOUNDATION Fieldbus, PROFIBUS PA, and 1-5 V low-power HART options
Seal systemDirect Mount and Tuned-System seal assemblies; welded-repairable transmitter connection
Process connectionFlanged ANSI/ASME, EN/DIN and JIS process connections
Wetted materials316L SST, Alloy C-276 and Tantalum diaphragm options
SafetySIL 2/3 certified to IEC 61508 by independent third party; NACE and hazardous-location approvals available
CommissioningLocal Operator Interface (LOI) for on-site commissioning without extra tools

Documents

FAQ

Q: Level range class? A: Up to about 300 psi (20.7 bar) depending on range code.

Q: Commissioning? A: Local Operator Interface (LOI) without extra tools.

Q: What should I send for a quote? A: Range/seal/protocol/materials/flange/SIL, qty, ship-to.

Links

ParameterValue
Process connectionFlanged ANSI/ASME, EN/DIN and JIS process connections
Wetted parts316L SST, Alloy C-276 and Tantalum diaphragm options
TypeRosemount 2051L liquid level transmitter (DP level with direct-mount / Tuned-System seals)
MeasurementHydrostatic level and specific gravity measurement using flanged DP level architecture
PressureLevel ranges up to about 300 psi (20.7 bar) depending on range code
Protocols4-20 mA HART, WirelessHART, FOUNDATION Fieldbus, PROFIBUS PA, and 1-5 V low-power HART options
Seal SystemDirect Mount and Tuned-System seal assemblies; welded-repairable transmitter connection
SafetySIL 2/3 certified to IEC 61508 by independent third party; NACE and hazardous-location approvals available
CommissioningLocal Operator Interface (LOI) for on-site commissioning without extra tools
DocumentEmerson Rosemount DP Level PDS 00813-0100-4016 Rev UD including 2051L ordering (emerson.com)