Amprobe

Amprobe MO-100 Milliohm Meter

SKU · 39116 · MO-100 Milliohmmeter · Brand: Amprobe
Available
Quote on request
No online payment · add lines to RFQ BOM

MO-100: 100 µΩ–2000 Ω; 4-wire; ±0.5%±2d; 100/10/1 mA; 8×AA. RFQ.

Download datasheet PDF

RFQ cart holds BOM lines only. Submit for engineering quote.

Key parameters

Accuracy
±0.5% of reading ±2 digits (−15 to 55 °C) with supplied leads
Measuring Ranges
200.0 mΩ / 2,000 mΩ / 20.00 Ω / 200.0 Ω / 2,000 Ω
Resolution
100 μΩ on lowest range
Test Currents
100 mA / 10 mA / 1 mA by range; test-current accuracy ±0.1%
Method
Four-terminal Kelvin measurement
Max Output Voltage
20 V (C1–C2)
Download datasheet PDF

Fits low-resistance winding and bond testing where you need an Amprobe MO-100—four-terminal measurement from 100 µΩ resolution through 2000 Ω across five ranges with ±0.5% of reading ±2 digits accuracy.

Key advantages

  • Ranges — 200.0 mΩ to 2000 Ω; 100 µΩ resolution on lowest
  • Accuracy — ±0.5% rdg ±2 digits (−15…55 °C)
  • Current — 100 / 10 / 1 mA by range; ±0.1%
  • Features — Auto-hold/auto-off; Rc/Rp lead checks
  • Power — 8× AA; sealed enclosure

Typical applications

  • Motor / transformer winding resistance.
  • Bond / continuity of joints.
  • Contact resistance checks.

Selection guide

  • Spare lead set
  • Quantity
  • Carry strap

Common mistakes

  • 2-wire instead of 4-wire.
  • Over-temperature without cool-down.
  • Energized circuit connection.

When to RFQ / what to tell us

  1. Quantity.
  2. Ship-to.

Request a Quote · Get selection help

Specs

SpecValue
SKU39116
BrandAmprobe
ModelMO-100
Product typeMilliohmmeter
TypeFour-terminal portable milliohm meter (Amprobe MO-100)
Ranges200.0 mΩ to 2000 Ω (5 ranges); resolution to 100 µΩ
Accuracy±0.5% of reading ±2 digits (−15…55 °C with supplied leads)
Test current100 mA / 10 mA / 1 mA by range; ±0.1% current accuracy
Power8× AA; auto-hold / auto-off
SizeAbout 250×190×110 mm; ~1.5 kg

Documents

FAQ

Q: Lowest resolution? A: 100 µΩ.

Q: Test currents? A: 100 mA, 10 mA, or 1 mA by range.

Q: What should I send for a quote? A: Quantity, ship-to.

Links

ParameterValue
Accuracy±0.5% of reading ±2 digits (−15 to 55 °C) with supplied leads
Measuring Ranges200.0 mΩ / 2,000 mΩ / 20.00 Ω / 200.0 Ω / 2,000 Ω
Resolution100 μΩ on lowest range
Test Currents100 mA / 10 mA / 1 mA by range; test-current accuracy ±0.1%
MethodFour-terminal Kelvin measurement
Max Output Voltage20 V (C1–C2)
Protection0.5 A HBC fuses on supply/current/voltage paths
SafetyIEC / EN 61010-1
Dimensions250 × 190 × 110 mm (9.8 × 7.5 × 4.3 in)
Weight1,500 g (3.3 lb)
Power8 × 1.5 V AA