Yokogawa

Yokogawa CW500 Power Quality Analyzer

SKU · 42730 · CW500 · Brand: Yokogawa
Available
Quote on request
No online payment · add lines to RFQ BOM

Yokogawa CW500: IEC 61000-4-30 Class S; ±0.2%; harmonics to 50th. RFQ.

Download datasheet PDF

RFQ cart holds BOM lines only. Submit for engineering quote.

Key parameters

Measuring range
Voltage RMS 600.0/1000 V ranges; current via clamp probes 96060–96066 (2 A to 3000 A types)
Accuracy
Voltage ±0.2% rdg ±0.2% rng (sine 40–70 Hz); current ±0.2% rdg ±0.2% rng + clamp accuracy; active power ±0.3% rdg ±0.2% rng + clamp (PF=1)
Output
Digital output; 2 CH analog DCV inputs; no process 4–20 mA transmitter output
Supply
AC 100–240 V 50/60 Hz 7 VA max; or 6× AA alkaline/NiMH (approx. 3 h LR6 backlight off)
Ambient temperature
Operating 0 to 45 °C, <85% RH; storage −20 to 60 °C
Display
3.5 in color TFT 320×240; update 1 s
Download datasheet PDF

Fits portable power quality surveys where you need a Yokogawa CW500—clamp-on power quality analyzer for 1P2W through 3P4W wiring with IEC 61000-4-30 Class S compliance, voltage accuracy ±0.2% of reading ±0.2% of range (40–70 Hz), and harmonics analysis to the 50th order.

Key advantages

  • PQ class — IEC 61000-4-30 Class S
  • Voltage — 600/1000 V RMS; ±0.2% rdg ±0.2% rng (40–70 Hz)
  • Wiring — 1P2W / 1P3W / 3P3W / 3P4W
  • Harmonics — To 50th; swell/dip/interrupt capture
  • Logging — SD card; optional Bluetooth

Typical applications

  • Facility PQ surveys.
  • Harmonic troubleshooting.
  • Event capture on feeders.

Selection guide

  • Clamp ratings
  • Bluetooth option
  • Logging duration

Common mistakes

  • Undersized clamps.
  • Wrong wiring map.
  • Missing SD capacity.

When to RFQ / what to tell us

  1. Clamp set/options.
  2. Quantity, ship-to.

Request a Quote · Get selection help

Specs

SpecValue
SKU42730
BrandYokogawa
ModelCW500
Product typePower Quality Analyzer
TypePortable clamp-on power quality analyzer (CW500)
Wiring1P2W / 1P3W / 3P3W / 3P4W
Voltage600/1000 V RMS; ±0.2% rdg ±0.2% rng (40–70 Hz)
PQIEC 61000-4-30 Class S; harmonics to 50th; swell/dip/interrupt
MemorySD card logging; optional Bluetooth (B1)

Documents

FAQ

Q: PQ class? A: IEC 61000-4-30 Class S.

Q: Harmonics? A: To the 50th order.

Q: What should I send for a quote? A: Clamps/options, quantity, ship-to.

Links

ParameterValue
Measuring rangeVoltage RMS 600.0/1000 V ranges; current via clamp probes 96060–96066 (2 A to 3000 A types)
AccuracyVoltage ±0.2% rdg ±0.2% rng (sine 40–70 Hz); current ±0.2% rdg ±0.2% rng + clamp accuracy; active power ±0.3% rdg ±0.2% rng + clamp (PF=1)
OutputDigital output; 2 CH analog DCV inputs; no process 4–20 mA transmitter output
SupplyAC 100–240 V 50/60 Hz 7 VA max; or 6× AA alkaline/NiMH (approx. 3 h LR6 backlight off)
Ambient temperatureOperating 0 to 45 °C, <85% RH; storage −20 to 60 °C
Display3.5 in color TFT 320×240; update 1 s
CommunicationUSB 2.0; SD card 2 GB; Bluetooth Ver 2.1+EDR Class2 on CW500-B1 (US/Canada/Japan)
ApprovalsIEC 61000-4-30 Class S; IEC 61000-4-15; IEC 61000-4-7; EN 61326-1 Class A; FCC/IC (Bluetooth model)
Sensor typePortable power quality analyzer with clamp-on current probes; IEC 61000-4-30 Ed.2 Class S
NotesSpecs from Yokogawa Bulletin CW500-01EN + IMCW500-01EN. Models CW500-B0 / CW500-B1.
Channels3 CH voltage + 4 CH current clamp + 2 CH DCV; wiring 1P2W/1P3W/3P3W/3P4W
HarmonicsUp to 50th harmonic (voltage/current/power); IEC 61000-4-7
Power Quality EventsSwell / dip / interrupt / transient overvoltage / inrush; sampling 24 µs; IEC flicker Pst/Plt
Dimensions120 (W) × 175 (H) × 68 (D) mm
WeightApprox. 900 g with battery
Safety RatingEN 61010-1 CAT IV 300 V / CAT III 600 V / CAT II 1000 V Pollution degree 2