Honeywell DR4500 Circular Chart Recorder

SKU · 25912 · DR4500 Classic Recorder · Brand: Honeywell
Available
Quote on request
No online payment · add lines to RFQ BOM

Honeywell DR4500: 12 in; pen-drawn Classic traces; 1-pen or 2-pen models; T/C, RTD, mA, V; 3 samples/s. RFQ.

Download datasheet PDF

RFQ cart holds BOM lines only. Submit for engineering quote.

Key parameters

Display
Vacuum fluorescent alphanumeric; 6-digit PV + 8-digit secondary; 21-segment deviation bargraph
Chart
12-inch circular chart; 5000+ preprinted charts available; pen-drawn analog traces (Classic)
Pens Channels
One-pen (1 input) or two-pen (2 inputs) models
Input Types
Thermocouple, RTD, 4–20 mA, 0–10 V and other low-level actuations; user-configurable type/range
Sampling Rate
Each input sampled 3 times per second
Digital Indication Accuracy
1 digit
Download datasheet PDF

Fits 12-inch pen-drawn circular chart recording where you need a Honeywell DR4500 Classic. One- or two-pen models with T/C, RTD, 4–20 mA, 0–10 V and other actuations sampled 3×/s, VFD display with 6-digit PV + deviation bargraph, optional 1–2 PID controllers (Accutune II, fuzzy overshoot), integral transmitter power, optional Modbus RS-485, soft alarms / relays, optional totalizers, and NEMA4X door option—distinct from DR4500 Truline printhead models.

Key advantages

  • Chart — 12 in; pen-drawn Classic traces
  • Pens — 1-pen or 2-pen models
  • Inputs — T/C, RTD, mA, V; 3 samples/s
  • Control — Optional PID; Accutune II; fuzzy overshoot
  • Options — Modbus RS-485; totalizers; NEMA4X door

Typical applications

  • Regulated pen-chart records.
  • Food/pharma circular charts.
  • Panel circular recording with optional PID.

Selection guide

  • 1-pen vs 2-pen
  • Classic vs Truline (33896)
  • PID / Modbus / NEMA4X options

Common mistakes

  • Ordering Truline when pen-drawn Classic is required.
  • Wrong input actuation.
  • Ignoring chart/consumable supply.

When to RFQ / what to tell us

  1. Pens, inputs, PID/Modbus/door, quantity, ship-to.

Request a Quote · Get selection help

Specs

SpecValue
SKU25912
BrandHoneywell
ModelDR4500 Classic Recorder
Product typeCircular Chart Recorder
Chart12-inch circular chart; 5000+ preprinted charts available; pen-drawn analog traces (Classic)
Pens/channelsOne-pen (1 input) or two-pen (2 inputs) models
Input typesThermocouple, RTD, 4–20 mA, 0–10 V and other low-level actuations; user-configurable type/range
Sampling rateEach input sampled 3 times per second
Digital accuracy1 digit
Input impedance4–20 mA: 250 Ω; 0–10 V: 200 kΩ; others: 10 MΩ
DisplayVacuum fluorescent alphanumeric; 6-digit PV + 8-digit secondary; 21-segment deviation bargraph
ControlOptional 1 or 2 PID digital controllers (On-Off, PID-A, PID-B, PD with manual reset); Accutune II™; fuzzy overshoot suppression
Transmitter powerIntegral 22–26 Vdc (50 mAdc @ 24 Vdc) for up to two transmitters
CommunicationsOptional Modbus RS-485
AlarmsIntegral soft alarms; optional SPST alarm relays
EnclosureMolded case, panel or surface mount; gasketed door with glass or acrylic; optional UL/FM NEMA4X door
TotalizerOptional one or two 8-digit totalizers with multiplier and low-flow cutoff

Documents

FAQ

Q: vs Truline? A: Classic is pen-drawn; Truline uses printhead on blank heat-sensitive charts.

Q: Sampling? A: Each input sampled 3 times per second.

Q: What should I send for a quote? A: Pens/inputs/options, quantity, ship-to.

Links

ParameterValue
DisplayVacuum fluorescent alphanumeric; 6-digit PV + 8-digit secondary; 21-segment deviation bargraph
Chart12-inch circular chart; 5000+ preprinted charts available; pen-drawn analog traces (Classic)
Pens ChannelsOne-pen (1 input) or two-pen (2 inputs) models
Input TypesThermocouple, RTD, 4–20 mA, 0–10 V and other low-level actuations; user-configurable type/range
Sampling RateEach input sampled 3 times per second
Digital Indication Accuracy1 digit
Input Impedance4–20 mA: 250 Ω; 0–10 V: 200 kΩ; others: 10 MΩ
ControlOptional 1 or 2 PID digital controllers (On-Off, PID-A, PID-B, PD with manual reset); Accutune II™; fuzzy overshoot suppression
Transmitter PowerIntegral 22–26 Vdc (50 mAdc @ 24 Vdc) for up to two transmitters
CommunicationsOptional Modbus RS-485
AlarmsIntegral soft alarms; optional SPST alarm relays
EnclosureMolded case, panel or surface mount; gasketed door with glass or acrylic; optional UL/FM NEMA4X door
Span Response6 s maximum with no filtering
TotalizerOptional one or two 8-digit totalizers with multiplier and low-flow cutoff