Image unavailable
Image unavailable
Bacharach
Bacharach H-10 PRO Refrigerant Leak Detector
Quote on request
No online payment · add lines to RFQ BOM
H-10 PRO: heated diode; 0.006 oz/yr; R-410A/134a/HFO; 1 s response. RFQ.
Download datasheet PDF
RFQ cart holds BOM lines only. Submit for engineering quote.
Key parameters
Type
Portable heated-diode universal refrigerant leak detector (H-10 PRO)
Refrigerants
Non-flammable CFC/HFC/HCFC/HFO including R-410A, R-134a, R-404A, HFO-1234yf/ze
Sensitivity
0.006 oz/yr stationary; 0.1 oz/yr moving (SAE J2791)
Response Time
1 second
Indicators
Visual red LED in probe tip + audible (speaker or headphones)
Probe
4.5 ft (1.37 m) flexible probe
Fits HVAC/R leak hunting where you need a Bacharach H-10 PRO—portable heated-diode universal detector for non-flammable CFC/HFC/HCFC/HFO refrigerants including R-410A, R-134a, R-404A and HFO-1234yf/ze, with sensitivity 0.006 oz/yr stationary and 0.1 oz/yr moving (SAE J2791) and about 1 second response.
Key advantages
- Sensor — Heated-diode universal refrigerant detector
- Refrigerants — CFC/HFC/HCFC/HFO incl. R-410A, R-134a, HFO-1234yf/ze
- Sensitivity — 0.006 oz/yr stationary; 0.1 oz/yr moving (SAE J2791)
- Response — About 1 second
- Indicators — Probe-tip red LED + audible
Typical applications
- HVAC refrigerant leak surveys.
- Cold-room leak location.
- Service truck leak detection.
Selection guide
- Spare tips / filters
- Headphones
- Battery pack
Common mistakes
- Using on flammables outside rating.
- Dirty tip filters.
- Air drafts masking leaks.
When to RFQ / what to tell us
- Accessories.
- Quantity, ship-to.
Request a Quote · Get selection help
Specs
| Spec | Value |
|---|---|
| SKU | 41112 |
| Brand | Bacharach |
| Model | H-10 PRO Refrigerant Leak Detector |
| Product type | Refrigerant Leak Detector |
| Type | Portable heated-diode universal refrigerant leak detector (H-10 PRO) |
| Refrigerants | Non-flammable CFC/HFC/HCFC/HFO including R-410A, R-134a, R-404A, HFO-1234yf/ze |
| Sensitivity | 0.006 oz/yr stationary; 0.1 oz/yr moving (SAE J2791) |
| Response time | 1 second |
| Indicators | Visual red LED in probe tip + audible (speaker or headphones) |
Documents
FAQ
Q: Sensitivity? A: 0.006 oz/yr stationary; 0.1 oz/yr moving (SAE J2791).
Q: Response? A: About 1 second.
Q: What should I send for a quote? A: Accessories/quantity, ship-to.
Links
| Parameter | Value |
|---|---|
| Type | Portable heated-diode universal refrigerant leak detector (H-10 PRO) |
| Refrigerants | Non-flammable CFC/HFC/HCFC/HFO including R-410A, R-134a, R-404A, HFO-1234yf/ze |
| Sensitivity | 0.006 oz/yr stationary; 0.1 oz/yr moving (SAE J2791) |
| Response Time | 1 second |
| Indicators | Visual red LED in probe tip + audible (speaker or headphones) |
| Probe | 4.5 ft (1.37 m) flexible probe |
| Power | Battery or 100–240 VAC wall adapter (N. American / international plug kits) |
| Part Numbers | 3015-8004 (N. American plug); 3015-8005 (international plugs) |
| Not For | Not for combustible/flammable A2/A3 refrigerants or hazardous locations |
| Brand Line | MSA Bacharach H-10 PRO |