Image unavailable
Image unavailable
VEGA
VEGA VEGATRENN 141 Single Channel Separator
Quote on request
No online payment · add lines to RFQ BOM
VEGA VEGATRENN 141: single-channel active Ex separator; 4–20 mA/HART; 21…16.5 V. RFQ.
Download datasheet PDF
RFQ cart holds BOM lines only. Submit for engineering quote.
Key parameters
Supply
AC 24…230 V (−15%/+10%) 50/60 Hz; DC 24…65 V (−15%/+10%)
Ambient temperature
−20…+60 °C (−4…+140 °F)
Mounting
DIN rail 35×7.5 mm per EN 50022/60715
Channels
Single channel active Ex separator
Sensor Input
1 × 4…20 mA/HART (up to 5× HART multidrop)
Input Type
Active (sensor powered by VEGATRENN 141)
Fits single-channel Ex signal separation where you need a VEGA VEGATRENN 141. Active separator powering one 4…20 mA/HART sensor loop (up to 5× HART multidrop), terminal voltage 21…16.5 V DC at 4…20 mA with 24 V DC off-load (±1 V), and one active 4…20 mA/HART output with off-load under 15.5 V DC.
Key advantages
- Channels — Single active Ex separator
- Input — 4…20 mA/HART (to 5× multidrop)
- Power — Sensor powered by separator
- Terminal V — 21…16.5 V at 4…20 mA
- Output — Active 4…20 mA/HART
Typical applications
- Ex barrier / separator loops.
- HART multidrop separation.
- Single-channel 4–20 isolation.
Selection guide
- Ex approvals
- HART multidrop count
- DIN accessories
Common mistakes
- Passive sensor expectation.
- Too many multidrop devices.
- Ignoring terminal voltage drop.
When to RFQ / what to tell us
- Approvals/options.
- Quantity, ship-to.
Request a Quote · Get selection help
Specs
| Spec | Value |
|---|---|
| SKU | 582268 |
| Brand | VEGA |
| Model | VEGATRENN 141 |
| Product type | Signal Separator |
| Channels | Single channel active Ex separator |
| Sensor input | 1 × 4…20 mA/HART (up to 5× HART multidrop) |
| Input type | Active (sensor powered by VEGATRENN 141) |
| Terminal voltage | 21…16.5 V DC at 4…20 mA; off-load 24 V DC (±1 V) |
| Output | 1 × active 4…20 mA/HART; off-load <15.5 V DC |
Documents
FAQ
Q: Channels? A: Single.
Q: Input? A: Active 4…20 mA/HART.
Q: What should I send for a quote? A: Approvals/options, quantity, ship-to.
Links
| Parameter | Value |
|---|---|
| Supply | AC 24…230 V (−15%/+10%) 50/60 Hz; DC 24…65 V (−15%/+10%) |
| Ambient temperature | −20…+60 °C (−4…+140 °F) |
| Mounting | DIN rail 35×7.5 mm per EN 50022/60715 |
| Channels | Single channel active Ex separator |
| Sensor Input | 1 × 4…20 mA/HART (up to 5× HART multidrop) |
| Input Type | Active (sensor powered by VEGATRENN 141) |
| Terminal Voltage | 21…16.5 V DC at 4…20 mA; off-load 24 V DC (±1 V) |
| Power Consumption | Max 3 W (15 VA) |
| Protection Rating | IP20; Protection class II; Pollution degree 2 |
| Hart | Bidirectional HART via front sockets or terminals |
| Sil | SIL2 qualification |