Image unavailable
Image unavailable
Carlo Gavazzi DAA01 Delay-on-Operate Timer
SKU · 48768 · Carlo Gavazzi Type DAA01 Timer
Quote on request
No online payment · add lines to RFQ BOM
DAA01: DIN delay-on-operate, 0.1 s–100 h, multi-voltage. RFQ + selection help.
RFQ cart holds BOM lines only. Submit for engineering quote.
Key parameters
Range
—
Accuracy
—
Output
—
DIN-rail delay-on-operate timer with seven knob-selectable ranges from 0.1 s to 100 h — multi-voltage supply, ≤0.2% repeatability, and 8 A SPDT or dual SPDT relay outputs in a 22.5 mm housing.
Key advantages
- Wide time span — Seven ranges covering 0.1 s…100 h with knob setting.
- Multi-voltage — Combined AC/DC supplies (e.g. DAA01CM24: 24 VDC and 24–240 VAC; D versions 24–240 VAC/DC).
- Relay power — 8 A SPDT or 2× 8 A SPDT; second relay selectable instantaneous or delayed via DIP.
- Repeatability ≤0.2% — Setting accuracy ≤5%; EN 61812-1 timer specs.
- DIN Euronorm — 22.5 mm D-housing (plug-in PAA01 sibling); UL/CSA/RINA (DAA01) approvals per datasheet.
Typical applications
- Power-on delay sequencing for motors, heaters, and process starts.
- Panel builders needing a compact multi-voltage on-delay relay.
- Machine control where a second contact must be instantaneous or delayed.
- Retrofit of older on-delay timers in 22.5 mm DIN space.
Selection guide
- Output — 1× SPDT (C) vs 2× SPDT (D).
- Supply code — CM24 vs DM24 (and plug-in PAA01 equivalents).
- Mounting — DIN-rail DAA01 vs plug-in PAA01.
- Time range — Confirm the longest delay you need within 100 h.
Common mistakes
- Expecting trigger-start delay — DAA01 is automatic start on power apply.
- Undersizing contacts for inductive loads — use AC15/DC13 ratings, not only AC1.
- Ignoring ≥200 ms supply interruption needed for full reset.
- Ordering plug-in PAA01 when the panel only has DIN rail.
When to RFQ / what to tell us
- DAA01C/D + supply code (or PAA01); quantity; ship-to.
Request a Quote · Get selection help
Specs
| Spec | Value |
|---|---|
| SKU | 48768 |
| Brand | Carlo Gavazzi |
| Model | DAA01 (PAA01 plug-in sibling) |
| Product type | Delay-on-operate timer |
| Time ranges | 0.1–1 s … 10–100 h (7 knob ranges) |
| Repeatability | ≤0.2% |
| Setting accuracy | ≤5% |
| Output | 1 or 2 × SPDT, 8 A @ 250 VAC (AC1) |
| Supply examples | 24 VDC + 24–240 VAC (C); 24–240 VAC/DC (D) |
| Housing | 22.5 × 80 × 99.5 mm DIN (DAA01) |
| Operating temp | −20…+60 °C |
| Protection | IP20 |
| Approvals (OEM) | UL, CSA, RINA (DAA01), CE |
Documents
FAQ
Q: DIN or plug-in? A: DAA01 is DIN-rail; PAA01 is the plug-in housing sibling on the same datasheet.
Q: Can the second relay be instantaneous? A: Yes — DIP under the front door selects instantaneous or delayed for relay 2.
Q: What should I send for a quote? A: C/D output, supply code, DIN vs plug-in, quantity, ship-to.
Links
| Parameter | Value |
|---|---|
| Status | Specs pending OEM datasheet merge |