Carlo Gavazzi DCB51 Asymmetrical Recycler Timer

SKU · 49272 · Carlo Gavazzi Type DCB51 Asymmetrical Recycler Timer
Available
Quote on request
No online payment · add lines to RFQ BOM

DCB51: DIN asymmetrical recycler, ON/OFF first, 0.1 s–100 h. RFQ + selection help.

RFQ cart holds BOM lines only. Submit for engineering quote.

Key parameters

Range
—
Accuracy
—
Output
—

Ultra-slim 17.5 mm DIN asymmetrical recycler with independently set ON and OFF times from 0.1 s to 100 h — choose ON-first or OFF-first by a jumper, multi-voltage supply, and 5 A SPDT output.

Key advantages

  • Asymmetrical recycle — Separate T1/T2 knobs so ON and OFF periods need not match.
  • Aa / Ab modes — ON first (no A1–Y1 link) or OFF first (jumper A1–Y1).
  • 0.1 s…100 h — Seven knob ranges for each time channel.
  • Multi-voltage — 24 VDC and 24–240 VAC on DCB51CM24.
  • Mini-D housing — 17.5 × 81 × 67.2 mm DIN; UL/CSA; ≤0.2% repeatability.

Typical applications

  • Pulsed pumps, heaters, or solenoids with unequal ON/OFF duty.
  • Flashing beacon or alarm cadence control.
  • Compact DIN panels where 22.5 mm timers are too wide.
  • Automatic-start recycle sequences after power apply.

Selection guide

  • Mode — Wire A1–Y1 only when OFF-first (Ab) is required.
  • T1 vs T2 — Assign the longer period to the correct knob pair.
  • Supply — Confirm DCB51CM24 covers your control voltage.
  • Contact load — 5 A AC1; use AC15/DC13 figures for inductive loads.

Common mistakes

  • Leaving the A1–Y1 jumper when you wanted ON-first — mode will invert.
  • Setting both knobs to the same range and expecting a symmetrical recycler — use a dedicated symmetrical model if equal times are all you need.
  • Ignoring ≥200 ms supply interrupt for reset.
  • Oversizing inductive loads past the 2.5 A AC15 rating.

When to RFQ / what to tell us

  1. Confirm DCB51CM24; quantity; ship-to.

Request a Quote · Get selection help

Specs

SpecValue
SKU49272
BrandCarlo Gavazzi
ModelDCB51CM24
Product typeAsymmetrical recycler timer
FunctionsAa ON first; Ab OFF first
Time ranges0.1 s…100 h (independent T1/T2)
Repeatability≤0.2%
Output1× SPDT, 5 A @ 250 VAC (AC1)
Supply24 VDC +10/−15% and 24–240 VAC +10/−15%, 45–65 Hz
Housing17.5 × 81 × 67.2 mm DIN Mini-D
Operating temp−20…+60 °C
ProtectionIP20
Approvals (OEM)UL, CSA, CE

Documents

FAQ

Q: How do I pick ON-first vs OFF-first? A: No link on A1–Y1 = Aa (ON first). Jumper A1–Y1 = Ab (OFF first).

Q: Can ON and OFF times differ? A: Yes — that is the asymmetrical recycler purpose; each has its own range and fine knob.

Q: What should I send for a quote? A: Confirm DCB51CM24, quantity, ship-to.

Links

ParameterValue
StatusSpecs pending OEM datasheet merge