Rosemount

Rosemount PowerVUE 4x5 Fan/Damper Actuator

SKU · 42114 · PowerVUE 4x5 · Marca: Rosemount
Disponible
Cotización a solicitud
Sin pago en línea · líneas en BOM RFQ
Descargar datasheet PDF

RFQ solo líneas BOM. Envíe para cotización de ingeniería.

Parámetros clave

Notes
Specs from Emerson PowerVUE PDS 102-222.A01 (Nov 2011). Same Hagan actuator construction as legacy torque positioners.
Positioner Type
Rosemount PowerVUE PVD 405 — 4×5 torque-type floor-mounted fan/damper actuator (Hagan pneumatic drive + Fisher FieldVUE DVC)
Output Motion
5 in (127 mm) stroke, 80° shaft rotation
Stall Torque
400 ft-lb (542 N·m) at 100 psig (689 kPa) air supply
Max Friction Load
50% of control torque; max weight load 140 ft-lb (189 N·m)
Repeatability
±0.5% of full stroke or better
Descargar datasheet PDF
ParámetroValor
NotesSpecs from Emerson PowerVUE PDS 102-222.A01 (Nov 2011). Same Hagan actuator construction as legacy torque positioners.
Positioner TypeRosemount PowerVUE PVD 405 — 4×5 torque-type floor-mounted fan/damper actuator (Hagan pneumatic drive + Fisher FieldVUE DVC)
Output Motion5 in (127 mm) stroke, 80° shaft rotation
Stall Torque400 ft-lb (542 N·m) at 100 psig (689 kPa) air supply
Max Friction Load50% of control torque; max weight load 140 ft-lb (189 N·m)
Repeatability±0.5% of full stroke or better
Full Stroke Time3 s no-load
Input Signal4–20 mA with HART or FOUNDATION fieldbus (integral I/P via DVC5000/6000)
Air SupplyOperating 45–100 psig (310–689 kPa); recommended 100 psig; max cylinder 100 psig
Air Consumption10 scfm steady state
Temperature LimitWithout heater 40–122 °F (4.4–50 °C), 140 °F (60 °C) with increased maintenance; with heater −10–122 °F
Unit Weight~80 lb (36 kg) typical; shipping ~95 lb (43 kg)
OptionsMechanical air lock, manual lock, limit switches, 4–20 mA position feedback (HART), heater/thermostat 115 V 150 W