Honeywell

Honeywell Fire Sentry FS10-R Unitized Multi-Spectral Flame Detector

SKU · 103756 · FS10-R Fire Sentry System · Marca: Honeywell
Disponible
Cotización a solicitud
Sin pago en línea · líneas en BOM RFQ
Descargar datasheet PDF

RFQ solo líneas BOM. Envíe para cotización de ingeniería.

Parámetros clave

Approvals
FM; CE; Class I Div 1&2 Groups B,C,D; Class II Div 1&2 Groups E,F,G; Class III
Detection Technology
Multi-spectral digital electro-optical IR (Visible + Near-band IR + Wide-band IR)
Application
Electrostatic liquid/powder paint spray booths; NFPA 33 oriented Fire Sentry FS System 10 family
Response Time
ALERT 0.3 s (fireball); Fire Early Warning 1 s; Fire Alarm <5 s if fire continues
Field Of View
90° (±45° H/V)
Spectral Sensitivity
Visible 400–700 nm; Near Band IR 0.7–1.1 µm; Wide Band IR 0.7–3.5 µm
Descargar datasheet PDF
ParámetroValor
ApprovalsFM; CE; Class I Div 1&2 Groups B,C,D; Class II Div 1&2 Groups E,F,G; Class III
Detection TechnologyMulti-spectral digital electro-optical IR (Visible + Near-band IR + Wide-band IR)
ApplicationElectrostatic liquid/powder paint spray booths; NFPA 33 oriented Fire Sentry FS System 10 family
Response TimeALERT 0.3 s (fireball); Fire Early Warning 1 s; Fire Alarm <5 s if fire continues
Field Of View90° (±45° H/V)
Spectral SensitivityVisible 400–700 nm; Near Band IR 0.7–1.1 µm; Wide Band IR 0.7–3.5 µm
Sensitivity45 ft and 30 ft to 1 sq ft gasoline fire (per SS01149B)
Input Power24 VDC nominal (18–32 VDC regulated)
Power ConsumptionNormal ~85 mA; Alarm ~120 mA typical
OutputsAlert/Early Warning SPST N.O.; Fire Alarm SPST N.O.; Fault SPST N.O.; 1 A @ 24 VDC; RS-485
Self TestBuilt-in automatic through-the-lens self-test
Operating Temperature−40 to +85 °C (−40 to +185 °F); humidity 10–90% RH non-condensing
EnclosureCopper-free powder-coated aluminum or optional 316 SS; NEMA 3/4/4X; two ¾" NPT; ~1.7 kg aluminum
FamilyFire Sentry FS System 10 / FS10-R