Rosemount

Rosemount 975UR Ultraviolet Infrared Flame Detector

SKU · 43518 · 975UR Flame Detector · Marca: Rosemount
Disponible
Cotización a solicitud
Sin pago en línea · líneas en BOM RFQ
Descargar datasheet PDF

RFQ solo líneas BOM. Envíe para cotización de ingeniería.

Parámetros clave

Approvals
ATEX; IECEx; FM; CSA; other regional Ex approvals per PDS
Sensing
Combined ultraviolet (0.185–0.260 µm) and infrared (4.3–4.8 µm) flame detection for hydrocarbon fires
Response Time
Ultra-fast response under 20 ms for flash fires (typical selectable settings)
Detection Range
Typical gasoline/n-heptane detection on the order of ~28 m (93 ft) per PDS
Field Of View
Approximately 100° horizontal × 95° vertical (per product documentation)
Outputs
Relays, 4–20 mA, HART, RS-485 Modbus
Descargar datasheet PDF
ParámetroValor
ApprovalsATEX; IECEx; FM; CSA; other regional Ex approvals per PDS
SensingCombined ultraviolet (0.185–0.260 µm) and infrared (4.3–4.8 µm) flame detection for hydrocarbon fires
Response TimeUltra-fast response under 20 ms for flash fires (typical selectable settings)
Detection RangeTypical gasoline/n-heptane detection on the order of ~28 m (93 ft) per PDS
Field Of ViewApproximately 100° horizontal × 95° vertical (per product documentation)
OutputsRelays, 4–20 mA, HART, RS-485 Modbus
Power18–32 Vdc nominal supply
OpticsHeated optics to reduce condensation/icing effects
EnclosureRugged flame-detector housing for hazardous industrial areas
DiagnosticsBuilt-in self-test / BIT features per 975 family
Special FeaturesSelectable UV, IR, or combined sensing logic; part of Rosemount 975 flame detector family
Product Type Note975UR UV/IR variant; distinct from 975MR multispectrum IR (SKU 43516 in-flight)