Image unavailable
Image unavailable
AEMC
AEMC 8220 Power Quality Analyzer & Meter
Cotización a solicitud
Sin pago en línea · líneas en BOM RFQ
Descargar datasheet PDF
RFQ solo líneas BOM. Envíe para cotización de ingeniería.
Parámetros clave
Supply
Six 1.5 V AA alkaline (≥8 h display on)
Voltage Trms
Phase-to-phase 660 V; phase-to-neutral 600 V
Current Trms
Probe dependent: MN to 240 A; MR to 1000 Aac/1400 Adc; AmpFlex to 6500 A
Frequency
40 to 70 Hz
Harmonics
1st to 50th; THD-F and THD-R for V and I
Power Energy
kW, kvar, kVA, PF, DPF; energy kWh/kvarh/VAh; inrush capture
| Parámetro | Valor |
|---|---|
| Supply | Six 1.5 V AA alkaline (≥8 h display on) |
| Voltage Trms | Phase-to-phase 660 V; phase-to-neutral 600 V |
| Current Trms | Probe dependent: MN to 240 A; MR to 1000 Aac/1400 Adc; AmpFlex to 6500 A |
| Frequency | 40 to 70 Hz |
| Harmonics | 1st to 50th; THD-F and THD-R for V and I |
| Power Energy | kW, kvar, kVA, PF, DPF; energy kWh/kvarh/VAh; inrush capture |
| Sampling | 256 samples/cycle; stores up to 99 snapshot sets |
| Communications | Optically isolated USB; DataView software |
| Safety Rating | EN 61010, 600 V CAT III, IP54 |
| Form Factor | 8.3 × 4.3 × 2.4 in (211 × 108 × 60 mm); 1.9 lb (0.88 kg) |
| Family | AEMC Model 8220 (discontinued; superseded by PEL series per OEM) |