Dwyer Instruments

Dwyer CDTV Carbon Dioxide/VOC Transmitter

SKU · 45416 · CDTV · Бренд: Dwyer Instruments
В наличии
Цена по запросу
Без онлайн-оплаты · строки в RFQ BOM
Скачать datasheet PDF

RFQ только BOM. Отправьте для инженерного КП.

Ключевые параметры

Measuring range
CO2 0–2000 or 0–5000 ppm; VOC 0–2000 ppm CO2-equivalent
Accuracy
CO2 ±40 ppm + 3% of reading
Output
Current 0/4–20 mA class (jumper) and voltage 0/1–5 or 0/2–10 VDC; optional SPST relay 2 A @ 30 VDC
Supply
16–35 VDC / 19–28 VAC; average 2 W, peak 3.75 W
Protection
Duct mount NEMA 4X (IP66) for housing; wall mount IP20
Ambient temperature
32 to 122 °F (0 to 50 °C)
Скачать datasheet PDF
ПараметрЗначение
Measuring rangeCO2 0–2000 or 0–5000 ppm; VOC 0–2000 ppm CO2-equivalent
AccuracyCO2 ±40 ppm + 3% of reading
OutputCurrent 0/4–20 mA class (jumper) and voltage 0/1–5 or 0/2–10 VDC; optional SPST relay 2 A @ 30 VDC
Supply16–35 VDC / 19–28 VAC; average 2 W, peak 3.75 W
ProtectionDuct mount NEMA 4X (IP66) for housing; wall mount IP20
Ambient temperature32 to 122 °F (0 to 50 °C)
DisplayPer model/options on OEM datasheet
ApprovalsCE
MountingWall or duct
Sensor typeSingle-beam dual-wavelength NDIR CO2 + MEMS metal-oxide VOC
NotesSeries CDTV CO2/VOC transmitter for demand-control ventilation and odor control. Specs from Dwyer CDTV datasheet.
Response TimeCO2 2 min for 99% step; VOC 5 min