Image unavailable
Image unavailable
Honeywell
Honeywell FS20X Fire Sentry Flame Detector
Цена по запросу
Без онлайн-оплаты · строки в RFQ BOM
Скачать datasheet PDF
RFQ только BOM. Отправьте для инженерного КП.
Ключевые параметры
Approvals
FM / ATEX Ex d / CU-TR / INMETRO; SIL 2 capable; EN54-10 option; FM 3260 performance
Type
Honeywell FS20X multi-spectrum UV / Dual IR / VIS fire and flame detector
Field Of View
90 degree horizontal cone of vision (+/-45 deg from on-axis)
Detection Range
Very high about 60 m / high 45 m / medium 30 m / low 15 m (switch selectable) to 0.1 m2 heptane fire
Response Time
About 3-5 s to 0.1 m2 n-Heptane at 30 m; 3-10 s at 60 m (very high sensitivity)
Spectral
UV 185-260 nm; Visible 400-700 nm; Near Band IR 0.7-1.1 um; WideBand IR 1.1-3.5 um
| Параметр | Значение |
|---|---|
| Approvals | FM / ATEX Ex d / CU-TR / INMETRO; SIL 2 capable; EN54-10 option; FM 3260 performance |
| Type | Honeywell FS20X multi-spectrum UV / Dual IR / VIS fire and flame detector |
| Field Of View | 90 degree horizontal cone of vision (+/-45 deg from on-axis) |
| Detection Range | Very high about 60 m / high 45 m / medium 30 m / low 15 m (switch selectable) to 0.1 m2 heptane fire |
| Response Time | About 3-5 s to 0.1 m2 n-Heptane at 30 m; 3-10 s at 60 m (very high sensitivity) |
| Spectral | UV 185-260 nm; Visible 400-700 nm; Near Band IR 0.7-1.1 um; WideBand IR 1.1-3.5 um |
| Operating Voltage | 24 Vdc nominal (18-32 Vdc regulated) |
| Power Consumption | About 85 mA operating @ 24 Vdc; about 135 mA alarm; heater adds about 155 mA |
| Outputs | Alarm/Fault/Aux relays; 0-20 mA stepped analog (source/sink); RS-485 Modbus / FireBus II; optional HART |
| Document | Honeywell FS20X datasheet DS01144 (prod-edam.honeywell.com) |