Image unavailable
Image unavailable
Dwyer Instruments
Dwyer Series 1950 Explosion-Proof Differential Pressure Switch
Цена по запросу
Без онлайн-оплаты · строки в RFQ BOM
Скачать datasheet PDF
RFQ только BOM. Отправьте для инженерного КП.
Ключевые параметры
Measuring range
Setpoint models from 0.07–0.15 in w.c. up through 4–20 in w.c.; 1950P models 0.5–50 psid
Accuracy
Repeatability governed by model deadband tables (see Bulletin E-57 / DS)
Output
SPDT switch (common / NO / NC screw terminals)
Process connection
1/8 in female NPT high and low pressure ports
Electrical connection
1/2 in female NPT conduit
Approvals
UL; CSA; FM; CE
| Параметр | Значение |
|---|---|
| Measuring range | Setpoint models from 0.07–0.15 in w.c. up through 4–20 in w.c.; 1950P models 0.5–50 psid |
| Accuracy | Repeatability governed by model deadband tables (see Bulletin E-57 / DS) |
| Output | SPDT switch (common / NO / NC screw terminals) |
| Process connection | 1/8 in female NPT high and low pressure ports |
| Electrical connection | 1/2 in female NPT conduit |
| Approvals | UL; CSA; FM; CE |
| Mounting | Diaphragm in vertical position; two mounting holes on 4-7/8 in BC |
| Setpoint | External screw adjustment on housing top; approximate deadbands per model chart |
| Electrical Rating | 15 A @ 125/250/480 VAC; 1/8 HP @ 125 VAC; 1/4 HP @ 250 VAC (mica/phenolic silver) |
| Service | Air and non-combustible compatible gases only (use 1950G for combustible gases) |
| Enclosure Rating | NEMA 3 (IP54) weatherproof; NEMA 7 and 9 explosion-proof |
| Temperature Limits | −40 to 140 °F (−40 to 60 °C); model-specific limits for 1950P-8/15/25/50 and 1950-02 |
| Pressure Limits | Continuous: 1950 in-w.c. models 45 in w.c.; 1950P 35 psi (1950P-50: 70 psi); surge limits per DS |
| Weight | 3.25 lb (1.5 kg); 1950-02 about 4.4 lb (2 kg) |