Image unavailable
Image unavailable
Define Instruments
Define Instruments Javelin Loop-Powered Isolated Universal Transmitter
Цена по запросу
Без онлайн-оплаты · строки в RFQ BOM
Скачать datasheet PDF
RFQ только BOM. Отправьте для инженерного КП.
Ключевые параметры
Type
Define Instruments Javelin 2-wire loop-powered galvanically isolated universal transmitter
Inputs
Software-selectable mA, V, mV, RTD (PT100/PT1000), thermocouple, NTC, potentiometer
Isolation
Input/output galvanic isolation; 2500 V AC for 1 min test
Power
10.5-36 V DC loop; supply sensitivity < +/-0.005%/V FSO
Load
650 ohm at 24 V DC (50 ohm/V above 10.5 V DC)
Response
About 400 ms typical (10-90% about 300 ms)
| Параметр | Значение |
|---|---|
| Type | Define Instruments Javelin 2-wire loop-powered galvanically isolated universal transmitter |
| Inputs | Software-selectable mA, V, mV, RTD (PT100/PT1000), thermocouple, NTC, potentiometer |
| Isolation | Input/output galvanic isolation; 2500 V AC for 1 min test |
| Power | 10.5-36 V DC loop; supply sensitivity < +/-0.005%/V FSO |
| Load | 650 ohm at 24 V DC (50 ohm/V above 10.5 V DC) |
| Response | About 400 ms typical (10-90% about 300 ms) |
| Housing | 35 mm DIN-rail; slim about 12.5 mm wide; IP20; about 77 g |
| Programming | Define ToolBox via USB Bridge Key; no input signal/power needed during USB setup |
| Document | Define Instruments Javelin datasheet 25V03 (catalog.defineinstruments.com / vendor-mirrored OEM DS) |